Cable Termination Guidelines - GE Limitamp CR194 Installation Instructions Manual

Two-high vacuum control
Hide thumbs Also See for Limitamp CR194:
Table of Contents

Advertisement

CR194 Two-High
Vacuum Limitamp@ Control
NOTE:
If
the two metal barriers that form the rear cable
trough (See Figure 3.2) are mounted in the upper compart-
ment, they can be moved to the lower compartment
to form the
necessary trough.
Once
the motor
cables are terminated,
the cable lugs and the complete
motor
terminal
pads
must be taped to maintain
necessary
electrical
clear-
(See "Taping
Instructions
for 5kV" section).
Figure 32. View of cable trough barriers that mount
in top or bottom compartment
CABLE ENTRY FROM TOP
Step
1.
Cables
to the top starter
should
be run straight
into
the motor
terminals
using
the "upper
unit" area as
shown in the top view in Figure
50.
Step
2.
Cables
to the bottom
starter
should
be run in the mo-
tor cable
trough
using
the "lower unit" area as shown
in the top view in Figure
50. This cable
trough
is
formed
by two metal
barriers
in the left rear corner
of
the upper
compartment.
Once
the cables
enter
the
lower compartment
they can be formed
forward
to
align with the motor
terminals.
NOTE:
If
the two metal bawiers that form the rear cable
trough (See Figure 32) are mounted in the lower compart-
ment, they can be moved to the upPer compartment
to form
the necessary trough.
WARNING:
Once
the motor
cables are terminated,
the cable lugs and the complete
motor
terminal
pads
ances.
(See "Taping
Instructions
for 5kV" section).
Cable Termination Guidelines
The following
general
guidelines
apply whether
motor
cable
or incoming
power cable
is being
terminated
in
the Limitamp@
lineup.
In any installation,
cable
should
be prepared
for termination
in accordance
with the in-
structions
of the cable
manufacturer.
Step
1.
Pull in the cables
for maximum
clearance
between
phase,
ground
and other
cable
or wire runs.
Step
2.
Prepare
the cable
for termination
in accordance
with
the manufacturer' s
instructions.
Some
possible
termi-
nation
methods
are shown in Figures
33-38.
Step 3.
Bolt the cable
terminals
to the point
of termination.
Step 4.
If contact
between
the cable and an adjacent
bare bus
cannot
be avoided,
as well may be the case in some in-
coming
line situations,
tape the bus in the immediate
vi-
cinity of the cable contact
point so that the surface
creepage
distance
from the cable to the bare bus bar is at
least three
inches.
Thus the surface
creepage
from the
bare bus where the cable terminates
to the nearest
bare
part of the bus the cable touches
will be at least seven
inches.
(See "Taping
Instructions
for 5kV' section).
TERMINATION
OF NON-SHIELDED,
NON-LEAD-COVERED
CABLE
This cable
is generally
run through
rigid conduit
or
cable
raceways
and brought
into the enclosure
by the
use of conventional
cable
clamps
and conduit
fittings.
Refer
to Figures
33 & 34 for termination
details.
GE IRRASILQ
SPLICE TAPE
Figure 33. Termination
of rubber-insulated,
non-shielded,
non-lead-covered,
5000-volt cable
19

Advertisement

Table of Contents
loading

Table of Contents