Incoming Power Connections; Grounding - GE Limitamp CR194 Installation Instructions Manual

Two-high vacuum control
Hide thumbs Also See for Limitamp CR194:
Table of Contents

Advertisement

CR194 Two-High
Vacuum Limitamp@ Control
Step 3.
If the contactor
is a stationary
type, install and torque
the three load side connection
bolts to 16 ft-lb. (See
Figure 18), then attach the line cables to the bottom
of the fuse assembly and torque these connections
to
9 ft-lb. (See Figure 20).
WARNING:
Be absolutely
certain
that these bolts
are properly
installed
and torqued.
These are cur-
Step 4.
If the contactor
is a drawout type, reinstall
the two
positioning
bolts (See Figure 19).
Step 5.
Manually operate
the contactor
armature
and observe
that the mechanical
interlock
functions
properly.
Step 6.
Reconnect
the control
umbilical
cord to the contactoi
and be sure the retaining
wing nuts are tight. Installa-
tion of the contactor
is now complete.
WARNING:
Make certain
that all barriers
are re-
placed and bolted tightly into position.
Make sure
the line and load side terminations
of the station-
ary contactor
are torqued properly. If the contactor
is drawout type, make sure the positioning
bolts
are installed
properly.
Failure to perform
these op-
erations
could result in failure of the unit to oper-
ate safely and reliably.
Incoming Power Connections
The compact
design of the two-high vacuum
Limitamp' does not make it practical
to terminate
in-
coming power cables within the starter. The equip-
ment must either be bus spliced to existing equipment
or supplied with a separate
cable entrance
compart-
ment. If a separate
cable entrance
compartment
is sup-
plied, refer to the Outline
Summary & Outline
Details
sections of the drawings provided with the equipment
to determine
the recommended
location
for incoming
power cable entry. Also see the "Cable Termination
Guidelines"
section
of this instruction.
Grounding
All controller
enclosures
must be grounded,
and the
CR194 two-high vacuum Limitamp@ is equipped
with a
ground bus for that purpose.
The two-high ground bus
should be bus connected
to existing
equipment
or to a
separate
cable entrance
compartment.
Figure 28 shows
the ground bus as seen from the rear of the enclosure
with the back cover removed.
In order to accommodate
motor cable grounds,
each
starter cubicle
is equipped
with a ground bus link that
is connected
directly to the horizontal
ground bus.
See Figure 29.
Figure 28. Rear view of horizontal main and
ground bus with back covers removed
GRO
BUS
Figure 29. view of motor
terminal
area showing
ground bus lii
in lower starter

Advertisement

Table of Contents
loading

Table of Contents