Starting The Ups With Utility - PowerWalker VFI 10K ICT IoT 3/3 BI Manual

Uninterruptible power supply
Table of Contents

Advertisement

UPS Mode
Output voltage
Output frequency
Output
ESS function
Auto bypass
Auto restart
Short circuit auto clear
Overload pre-alarm
DC Start
Battery Auto Test
Deep discharge protection
Low bat warning
Low remaining time warning 0-999min
Battery
Restart battery level
Charger current
External battery setting
Dry in
Dry out
Communication
IoT function
Modbus TCP
Control Menu password
Setting Menu password
Password
Change Password
(1)
Site wiring fault function is only for single phase bypass input. If the utility power is IT system, the
site wiring fault function should be disabled.

5.6 Starting the UPS with utility

Startup preparation:
Before startup the UPS, please make sure that the wiring is securely connected,
otherwise there is a danger of electric shock.
[Normal mode], [ECO mode],
[CVCF mode]
[220V], [230V], [240V]
[Auto detection], [50Hz], [60Hz]
[Enabled], [Disabled]
[Enabled], [Disabled]
[Enabled], [Disabled]
[Enabled], [Disabled]
50%~105%
[Enabled], [Disabled]
[Every cycle] [Disabled]
[Enabled], [Disabled]
0%~100%
0~100%
[1-13A]
[Auto detection], [Manual AH setting]
Manual AH setting: [9-300AH]
[No function] [Start UPS] [Remote shut
down] [Maintenance bypass]
[load powered] [on battery] [Low
battery] [No Battery] [Bypass] [ups OK]
[Enabled], [Disabled]
[Enabled], [Disabled]
[Enabled], [Disabled]
[Enabled], [Disabled]
Old password
New password
Confirm password
44
Normal mode
230V
Auto detection
Disabled
Enabled
Enabled
Disabled
105%
Enabled
Every cycle
Enabled
0%
0min
0%
[4A] for 10-20KS
[1.4A] for 15K
[2A] for 10K/20K
[Auto detection]
/
No function
load powered
Disabled
Disabled
Enabled
Enabled
[4732]