3.4 Power cables connection

This chapter introduces how to wire AC IN/OUT cable to UPS in different mode, and
UPS connecting with EBM/MBP.
3.4.1 Input /Output wiring specification
Before wring UPS, upstream breaker and backfeed contactor should be configured to
avoid power backfeed to unity. And 'backfeed voltage danger' warning label should be
added in backfeed contactor or device. Before operating, UPS input should cut off, and
check all terminals voltage to avoid voltage dangerous. Backfeed contactor rating
current should be larger than UPS rating input current.
Below figures show the wiring system of UPS input.
Danger!
The rated current of the utility power switch must be greater than the UPS input
current, otherwise the utility power switch may be burnt!
Single phase input system
Three phase input system