Appendix A: Selection Of Kwh Meter & Current Transformer - Gree ME20-24/D1(T) Owner's Manual

Intelligent controller
Table of Contents

Advertisement

Intelligent Controller
9 Appendix A: Selection of KWH Meter & Current
Transformer
Selection scheme 1
KWH meter model: ENTES EPR-04S-96
Parameters of ENTES EPR-04S-96
(1) Measure the 3-phase voltage and electric current. Calculate the forward and
reverse active electricity quantity.
(2) Working voltage: 45-265V AC/DC.
(3) Measuring voltage: 10-300V AC (L-N), 10-500V AC (L-L).
(4) Frequency: 45-65Hz.
(5) Reference current: 0.05-5.5A.
(6) Communication port: RS-485 port.
(7) Communication protocol: Modbus RTU.
Current transformer: comply with the following parameters.
Parameters of Current Transformer.
(1) Rated voltage & frequency: 630V, 50Hz.
(2) Grade of accuracy: 1.
(3) Secondary rated current: 5A.
(4) Rated output load: 5VA.
(5) Rated primary current of current transformer: Select according to table 1.
Please use the current transformer made by a well-known brand with high
reliability.
Table 1: Reference Table of Load and Mutual-Inductance Ratio
Rated capacity of unit (HP)
≤18
20~36
38~74
76~88
Selection scheme 2
KWH meter model: Wattnode Modbus WNC-3D-240-MB
Parameters of WNC-3D-240-MB:
(1) Measure the 3-phase voltage and electric current. Calculate the forward and
reverse active electricity quantity.
Rated capacity of unit (kW)
≤50.4
56~101
106.4~207.2
212.8~246.4
26
Mutual-inductance ratio of current
transformer
50/5A
100/5A
200/5A
250/5A