Initial Setup; Selecting The System Features - heat-timer SQ-Elite-8S Installation And Operation Instruction Manual

Steam seqsuencing control
Table of Contents

Advertisement

6
Heat-Timer Corp.
Make sure you Have tHe rIgHt control
If you need the SQ-Elite to do additional tasks that either are not listed or do not know how to set them, contact Heat-Timer Corp.
Sales Department either by Phone (973)575-4004, Fax (973) 575-4052, or by E-mail support@heat-timer.com.
Having an Initial Setup Program will ease the setting of the SQ-Elite-8S and will provide the opportunity to utilize many of the energy
saving features available in the control and give more comfortable heat when needed.
The program should consist of the following:
Selecting the features that your system can utilize
Installation: Install the Control and sensors and its components
Setting the System Startup
Setting the System Settings
Setting the Stages

selectIng tHe systeM Features

The SQ-Elite-8S has been designed with Steam heating as the primary purpose. With this in mind, many of the SQ-Elite-8S features can
be utilized to ease, enhance, and improve your system performance. Some of these features are listed in this section.
set poInt or eXternal 4-20Ma set poInt
The SQ-Elite-8S can control the System Pressure either by maintaining an adjustable Set Point or by using an optional 4-20mA EMS
Interface (HT# 926741-00). The SQ-Elite-8S can receive an external Set Point as a 4 - 20mA signal from an EMS system using the
4-20mA EMS Interface.
pId or oss control logIc
The SQ-Elite-8S's PID can be used for applications where system reaction is slow and requires a long period to achieve or measure
the results. However, OSS can be used for applications where the load changes frequently and the sequencing must match the load
and its immediate change.
nuMber oF stages
The SQ-Elite-8S can be configured to control up to eight stages. It can control up to 24 stages by adding a maximum of two SQ-
Elite-EXT Extension Panels, each with eight stages.
control coMbustIon aIr daMper
The Combustion Air Damper output can control the equipment while utilizing the PROVE input to check the status on the Combustion
Air Damper End Switch or any other device before any stage is energized.
autoMatIc rotatIon aMong boIlers
Rotating the lead boiler to be activated on a call for output promotes even wear on all boilers. The SQ-Elite-8S has three modes of
rotation: Manual, First-On-First-Off, or Timed Rotation. This option automatically rotates boilers every selected period from one
hour to every 41(999 hours) days.
setback or day/nIgHt scHedulIng
Two Setback modes are available for the SQ-Elite-8S:
The Day/Night Scheduling provides an adjustable time-based schedule for the Setback.
The Setback mode uses an external signal to switch the operation of the SQ-Elite in and out of setback mode.

InItIal setup