Closed-loop Connector Sizes and Tightening Torque
J
The closed-loop connectors and tightening torques for various wire sizes are shown in Table 3.14.
Table
Wire Thickness [mm
Wiring Method
J
Use the following procedure to connect wires to the terminal block.
1. Loosen the terminal screws with a thin-slot screwdriver.
2. Insert the wires from underneath the terminal block.
3. Tighten the terminal screws firmly.
Strip the end for
5.5 mm if no
solderless ter-
minal is used.
Fig
Wiring Precautions
NOTE
1.
Separate PG Speed Control Card control circuit wiring (terminals TA1 and TA2) from main circuit wiring
and other high-power lines.
2. Use twisted-pair or shielded twisted-pair cables to connect the PG to prevent operating faults. Process
cable ends as shown in Figure 3.28. The maximum cable length is 100 m.
Connect to terminal
TA3 on the
VS-626MC5.
Fig
3. Connect the shield to the ground terminal.
4. Do not solder the wires to the control circuit terminals. The wires may not contact well with the control
circuit terminals if the wires are soldered.
5. The end of each wire connected to the control circuit terminals must be stripped for approximately
5.5 mm.
Closed-loop Connectors and Tightening Torques
3.14
Terminal
2
]
Screws
0.5
0.75
M3 5
M3.5
1.25
2
Thin-slot screwdriver
Solderless terminal or
wire without soldering
Wires
Connecting Wires to Terminal Block
3.27
Shield sheath
Insulate with tape.
3.28
Processing the Ends of Twisted-pair Cables
- 29
3.7 I nstalling and Wiring PG Speed Control Cards
Crimp Terminal Size
1.25 to 3.5
1.25 to 3.5
1.25 to 3.5
2 to 3.5
Control circuit
terminal block
Blade thickness: 0.6 mm max.
Armor
Do not connect here.
Tightening Torque (N m)
0.8
0 8
Blade of screwdriver
3.5 mm max.
3