Reduced Voltage Starting - Emotron MSF 2.0 Instruction Manual

Table of Contents

Advertisement

St Conel Street Nudgee SPS SP043 Electrical Switchboard Operation and Maintenance Manual (Whelan)
Some applications like conveyors or screws may need an ini-
tial torque boost. However, for many applications it can be
seen that the torque needed is much lower than the torque
delivered by the induction motor in a DOL start.
A common method to reduce both starting torque and cur-
rent is to decrease the motor voltage during starting. The
following figure shows how the motor's torque and current
characteristics are changed when the supply voltage is
reduced.
T/T
n
2.5
2
1.5
1
0.5
0
0
I/I
n
8
U
n
7
6
U
<U
2
5
4
U
<U
3
3
2
1
0
0
Fig. 6
Reduced voltage start
A general rule of thumb is that the torque at each operating
point is roughly proportional to the square of the current.
This means when the motor current is decreased by a factor
of two by means of reducing the supply voltage, the torque
delivered by the motor will be decreased by a factor of four
(approximately).
2
T ~ I
I
= 1/2 I
LV
I
= 1/3 I
LV
LV=low voltage
DOL=Direct on line
10
Description
Q-Pulse Id TMS484
Torque
0.5
Current
n
2
0.5
≈ 1/4 T
-> T
DOL
LV
DOL
≈ 1/9 T
-> T
DOL
LV
DOL
This relationship is the base for any starting method using
reduced voltage. It can be seen that the possibility of reduc-
ing the starting current depends on the correlation between
the motor's and the load's torque characteristic. For the com-
bination of an application with very low starting load and a
motor with very high starting torque, the starting current
may be reduced significantly by means of decreasing the
voltage during start. However, for applications with high
starting load it may – depending on the actual motor – not
be possible to reduce the starting current at all.
2.2

Reduced voltage starting

This section describes different starting methods which are
based on the reduced-voltage principle explained above. A
pump and its quadratic torque characteristic are used as an
example.
The star-delta starter is the simplest example of a reduced
U
n
voltage starter. The motor phases are first star connected; at
about 75% of nominal speed the phase connection is then
changed to delta. To enable star-delta start, both ends of all
U
<U
2
n
three motor windings have to be available for connection.
Moreover, the motor has to be dimensioned for the (higher)
U
<U
voltage in the delta connection. The following figure shows
3
2
the resulting torque and current characteristics.
n/n
n
1
T/T
2.. 5
n
2
1.5
1
0.5
0
n/n
n
I/I
8
1
n
7
6
5
4
3
2
1
0
0
Fig. 7
Star-delta start
Active 03/12/2013
Torque
0
0.5
Current
0.5
Emotron AB 01-4135-01r1
n/n
n
1
n/n
n
1
Page 15 of 372

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents