8.10.2 Status
Softstarter status
7 2 0
0
Range:
1-12
1
Stopped, no alarm
2
Stopped, alarm
3
Run with alarm
4
Acceleration
5
Full voltage
6
Deceleration
7
Bypassed
8
PFC
9
Braking
10
Slow speed forward
11
Slow speed reverse
Standby (waiting for Analogue start/stop or
12
Autoreset)
Digital Input Status
Status of the digital inputs 1- 4 from left to right. L or H are
displayed for input status low (open) or high (closed).
7 2 1
L L L L
Range:
LLLL-HHHH
Analogue/digital Input status
Status of the analogue/digital input when it is used as digital
input. L and H are displayed for input status low (open) and
high (closed).
7 2 2
L
Range:
L, H
Emotron AB 01-4135-01r1
Q-Pulse Id TMS484
Read-out
Softstarter status
Read-out
Digital input status
Read-out
Analogue/digital input status
Active 03/12/2013
Analogue/digital input value
Value on the analogue/digital input as a percentage of the
input range. This read-out depends on the configuration of
the analogue/digital input in menu [500], e.g. if the ana-
logue/digital input is configured for analogue start/stop
0-10 V/0-20 mA (alternative 6), an input signal of 4 V or
8 mA will be shown as 40%. However, if the analogue/dig-
ital input is configured for analogue start/stop 2.10 V/4-20
mA (alternative 7), an input signal of 4 V or 8 mA will be
shown as 25%.
7 2 3
Analogue/digital input value
0
Range:
0-100%
Relay status
Status of the relays K1 to K3 from the left to the right. L or
H are displayed for relay status low (opened) or high
(closed). The status described for relay K3 corresponds to
the status of terminal 3.
7 2 4
Relay status
L
L
L
Range:
LLL-HHH
Analogue Output value
Value on the analogue output as a percentage of the output
range. This read-out depends on the configuration of the
analogue output in menu [520], e.g. if the analogue/digital
input is configured for 0-10 V/0-20 mA (alternative 1) or
for 10-0 V/20-0 mA (alternative 3), an output signal of 4 V
or 8 mA will be shown as 40%. However, if the analogue
output is configured for 2-10 V/4-20 mA (alternative 2) or
10-2 V/20-4 mA (alternative 4), an output signal of 4 V or
8 mA will be shown as 25%.
7 2 5
Analogue Output value
0
Range:
0-100%
Functional description
Read-out
Read-out
Read-out
93