2.2 Option error

2.2.1 Feed-back board (SJ-FB)

Trip
Encorder wire cut
Over speed
Positioning error
Cnnection error

2.2.2 Digital-input option board (SJ-DG)

Trip
Option card error
2.2.3 Device- Net option board (SJ-DN)
The error display at the time of device network option board (SJ-DN) connection
Trip
DeviceNet communication error
Duplication MAC ID
External trip
Communication error of inverter
Contents
ü Wire break and/or loose connection of the encoder signal.
ü Encoder failure or used the encoder which is not line driver
output.
ü Used encoder without Z phase signal.
Detect when the motor rotation exceeds
(Maximum frequency)
(over speed detection level (P026))
Detects when the deviation between actual position and position
command exceeds 1,000,000 pulses.
It displays, when the poor connection with SJ-FB is detected.
contents
To detect the option card error(failure)
contents
It displays, when connection cutting and the timeout by
Bus-Off etc. occur at the time of operation by DeviceNet
instructions. (Trip by setup of P045 and P048)
It is shown that the apparatus of the same MAC ID
exists in the same network.
The instance of Control Supervisor object 1 and Force
by the attribute 17 Fault/Trip It displays, when set to 1.
It
displays,
when
a
communication between an inverter and a DeviceNet
option board.
2- 3
Digital
operator
display
Digital
operator
display
Digital
display
timeout
occurs
by
the
Remedy, advice
ü Check the wiring.
ü Replace recommended encoder.
ü Set SWENC-2 " OFF" on the card.
ü Tune Kp and J parameters which are
related to ASR to reduce the speed
overshoot.
ü Increase position loop gain of APR.
ü Decrease the input pulses per second of
the pulse train input.
ü Make sure the connection of the board
ü Make sure if the usage is proper
Remedy, advice
Make sure the connection of the board
Make sure if the usage is proper
Display of remote
operator
operator
ERR1***
OP1-0
OP2-0
OP1-1
OP2-1
OP1-2
OP2-2
OP1-9