Hitachi L300P Series Service Manual page 16

Hitachi inverter service manual
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

Function Mode
Code
Function name
Overload restriction
b021
selection
b022
Overload restriction level
Overload restriction limit
b023
constant
Overload restriction 2
b024
selection
b025
Overload restriction level 2
Overload restriction
b026
constant 2
Software lock mode
b031
selection
b100
Free V/f frequency 1
b101
Free V/f voltage 1
b102
Free V/f frequency 2
b103
Free V/f voltage 2
b104
Free V/f frequency 3
b105
Free V/f voltage 3
b106
Free V/f frequency 4
b107
Free V/f voltage 4
b108
Free V/f frequency 5
b109
Free V/f voltage 5
b110
Free V/f frequency 6
b111
Free V/f voltage 6
b112
Free V/f frequency 7
b113
Free V/f voltage 7
C001
Intelligent input 1 setting
C002
Intelligent input 2 setting
C003
Intelligent input 3 setting
C004
Intelligent input 4 setting
C005
Intelligent input 5 setting
Intelligent input1 a/b
C011
(NO/NC) selection
Intelligent input2 a/b
C012
(NO/NC) selection
Intelligent input3 a/b
C013
(NO/NC) selection
Intelligent input4 a/b
C014
(NO/NC) selection
Intelligent input5 a/b
C015
(NO/NC) selection
Input FW a/b (NO/NC)
C019
Selection
C021
Intelligent output 11 setting
C022
Intelligent output 12 setting
C026
Alarm relay output
C027
FM selection
C028
AM selection
C029
AMI selection
C031
Intelligent output 11 a/b
C032
Intelligent output 12 a/b
C036
Alarm relay output a/b
Overload advance notice
C040
signal output mode
Overload
advance
C041
level
Frequency arrival setting
C042
for acceleration.
Arrival frequency setting for
C043
deceleration.
C044
PID deviation setting level
00(invalid)/01(enabled on acceleration / constant speed)/02(enabled
0.50* rated current-1.50* rated current(A)
00(invalid)/01(valid on acceleration / constant speed)/02(valid on
0.50*rated current-1.50*rated current(A)
00(impossible to change the data except this item when SFT terminal
is ON)/01(impossible to change the data except setting frequency
item when SFT terminal is ON)/02(impossible to change the data
except this item)/03(impossible to change the data except setting
frequency item)/10(possible to change data on operating)
0.- Free V/f frequency2(Hz)
0.- Free V/f frequency3(Hz)
0.- Free V/f frequency4(Hz)
0.- Free V/f frequency5(Hz)
0.- Free V/f frequency6(Hz)
0.- Free V/f frequency7(Hz)
0 1 / (RV:Reverse is valid)/02(CF1:Multi-speed1)/ 03(CF2:Multi-speed2)/
04(CF3:Multi-speed3)/ 05(CF4:Multi-speed4)/ 0 6 (JG:Jogging)/
07(DB:External DC braking)/08(SET:2
09(2CH:two-stage adjustable speed)/11(FRS:Free-run)/
12(EXT:External trip)/13(USP:Unattended start protection)/
14(CS:commercial change)/15(SFT:software lock)/
16(AT:Analog input voltage/current select)/18(RS:Reset inverter)/
20(STA:3wire run)/ 21(STP:3wire keep)/22(F/R:3wire forward/reverse)/
23(PID:PID selection valid/invalid)/24(PIDC:PID integrating reset)/
27(UP:Remote control UP function)/
28(DWN:Remote control DOWN function)/
29(UDC:Remote control data clear)/31(OPE:Force operate o p e ) /
32(SF1:Multi-speed bit1)/
33(SF2:Multi-speed bit2)/34(SF3:Multi-speed bit3)/
35(SF4:Multi-speed bit4)/36(SF5:Multi speed bit5)/
37(SF6:Multi-speed bit6)/38(SF7:Multi-speed bit7)/
39(OLR:Overload restriction change)/no(NO:No assign)
00( RUN:running)/01(FA1:Frequency arrivaltype1 signal)/
02(FA2:frequency arrival type2 signal)/03(OL:Overload advance
notice signal)/04(OD:Output deviation for PID control)/05(AL:Alarm
signal)/06(FA3:Only setting frequency)/08( IP:On instantaneous stop/
09( UV:Under voltage)/11(RNT:RUN time over)/12(ONT:ON time
over)/
13( THM:thermal caution)
00(Output frequency)/01(Output current) /
03(Digital output frequency)/04(Output voltage)/
05(Input electric power)/06(thermal load rate)/07(LAD frequency)
00(Output frequency)/01(Output current)/04(Output voltage)/
05(Input electric power)/06(thermal load rate)/07(LAD frequency)
00(Output frequency)/01(Output current)/04(Output voltage)/
05(Input electric power)/06(Thermal load rate)/07(LAD frequency)
00(On accel. And decel, constant speed)/01(Only constant speed)
notice
0.0-2.0*rated current(A)
0.00-99.99/100.0-400.0(Hz)
0.00-99.99/100.0-400.0(Hz)
L300P Setting range
on constant speed)
0.10-30.00(s)
constant speed)
0.10-30.00(s)
0.-800.0(V)
0.-800.0(V)
0.-800.0(V)
0.-800.0(V)
0.-800.0(V)
0.-800.0(V)
0.-400.(Hz)
0.-800.0(V)
nd
control)/
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
0.0-100.0(%)
1- 13
Initial data
N o t e
-FE/-FU/-FR
01
Rated
current of
inverter
x 1.20
1.00
01
Rated
current of
inverter
x1.20
1.00
01
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
18
16
03/13/03
02
01
00
00
00/01/00
00
00
00
01
00
05
00
00
00
00
00
01
01
Inverter
rated current
0.00
0.00
3.0