Function mode
Code
Function name
Intelligent input 1 a/b
C011
(NO/NC) selection
Intelligent input 2 a/b
C012
(NO/NC) selection
Intelligent input 3 a/b
C013
(NO/NC) selection
Intelligent input 4 a/b
C014
(NO/NC) selection
Intelligent input 5 a/b
C015
(NO/NC) selection
Intelligent input 6 a/b
C016
(NO/NC) selection
Intelligent input 7a/b
C017
(NO/NC) selection
Intelligent input 8 a/b
C018
(NO/NC) selection
Input FW a/b (NO/NC)
C019
Selection
C021
Intelligent output 11 setting
C022
Intelligent output 12 setting
C023
Intelligent output 13 setting
C024
Intelligent output 14 setting
C025
Intelligent output 15 setting
C026
Alarm relay output
C027
FM selection
C028
AM selection
C029
AMI selection
C031
Intelligent output 11 a/b
C032
Intelligent output 12 a/b
C033
Intelligent output 13 a/b
C034
Intelligent output 14 a/b
C035
Intelligent output 15 a/b
C036
Alarm relay output a/b
Overload advance notice
C040
signal output mode
Overload
advance
C041
level
Frequency arrival setting for
C042
acceleration.
Arrival frequency setting for
C043
deceleration .
C044
PID deviation setting level
Frequency arrival setting for
C045
acceleration 2.
Arrival frequency setting for
C046
deceleration 2.
Over torque level setting
C055
(Forward-driving)
Over torque level setting
C056
(Reverse-regenerating)
Over torque level setting
C057
(Reverse-driving)
Over torque level setting
C058
(Forward-regenerating)
Thermal warning level
C061
setting
C062
Alarm code selection
Zero speed detection level
C063
setting
C070
Data command
Communicating transmission
C071
speed
C072
Communication code
C073
Communication bit
C074
Communication parity
C075
Communication stop bit
C078
Communication waiting time
C081
O adjustment
C082
OI adjustment
C083
O2 adjustment
C085
Thermistor adjustment
C086
AM offset adjustment
C087
AMI adjustment
C088
AMI offset adjustment
(Note) < > indicate the setting range of 75 to 150kW
00(RUN:running)/01(FA1:Frequency arrival type1 signal)/
02(FA2:over setting frequency)/03( OL:Overload advance notice signal)/
04( OD:Output deviation for PID control)/05( AL:Alarm signal)/
06(FA3:Only setting frequency)/07( OTQ:Over-torque signal)/
08( IP:On instantaneous stop)/09( UV:Under voltage)/
10(TRQ:Torque limit)/11(RNT:RUN time over/12(ONT:ON time over)/
13(THM:thermal caution)/19( BRK:Brake release signal)/
20( BER:Brake error signal)/21( ZS:Zero speed detect signal)/
22(DSE:Speed error over signal)/23( POK:Positioning completion signal)
24(FA4:Over frequency 2 signal)/25(FA5:Only setting frequency)/
26(OL2: Overload advance notice signal 2)
(Intelligent output terminal 11-13 or 11-14 becomes AC0-AC2 or AC0-AC3
(Can:Alarm cord output) forcibly when alarm cord output is selected in
C062)
00(Output frequency)/01(Output current) /02(Output torque)/
03(Digital output frequency)/04(Output voltage)/
05(Input electric power)/06(thermal load rate)/07(LAD frequency)
00(Output frequency)/01(Output current)/02(Output torque)/
04(Output voltage)/05(Input electric power)/06(thermal load rate)/
07(LAD frequency)
00(Output frequency)/01(Output current)/02(Output torque)/
04(Output voltage)/05(Input electric power)/
06(Thermal load rate)/07(LAD frequency)
00(On accel. And decel, constant speed)/01(Only constant speed)
notice
0.00-99.99/100.0-400.0(Hz)
0.00-99.99/100.0-400.0(Hz)
0.00-99.99/100.0-400.0(Hz)
0.00-99.99/100.0-400.0(Hz)
00(Invalid)/01(3bit)/02(4bit)
02(operator)/03(RS485)/04(option1)/05(option2)
03(2400bps)/04(4800bps)/05(9600bps)/06(19200bps)
00(no parity name)/01(even parity)/02(odd parity)
0.-9999./1000-6553(10000-65530)
0.-9999./1000-6553(10000-65530)
0.-9999./1000-6553(10000-65530)
SJ300 Setting range
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
00(NO)/01(NC)
0.0-2.0*rated current(A)
0.0-100.0(%)
0.-200.(%) <0.-180.>
0.-200.(%)
0.-200.(%) <0.-180.>
0.-200.(%) <0.-180.>
0.-100.(%) <0.-180.>
0.00-99.99/100.(Hz)
02(loop-back test)
1. - 32.
7(7bit)/8(8bit)
1(bit)/2(bit)
0.-1000.(ms)
0.0 - 1000.
0.0 - 10.0(V)
0. - 255.
0. - 20.0( mA)
1- 6
Initial data
Note
-FE/-FU/-F
00
00
00
00
00
00/01/00
00
00
00
01
00
03
07
08
05
00
00
00
00
00
00
00
00
01
01
Inverter
rated current
0.00
0.00
3.0
0.00
0.00
100.
100.
100.
100.
80.
00
0.00
02
04
1.
7
00
1
0.
Setting on
forwarding
Setting on
forwarding
Setting on
forwarding
105.0
0.0
80
4.0