Ld0.T1Pttr1 Thermal Overload Values (1); Ld0.Darrec1 Autorecloser (1); Ld0.Secrsyn1 Synchrocheck (1) - ABB Relion RER615 Manual

Hide thumbs Also See for Relion RER615:
Table of Contents

Advertisement

Section 2
IEC 60850-5-101/104 data mappings
Object type
Addr
21
10111
21
10112
21
10005
21
10006
21
10007
21
10003
21
10004
21
10009
21
10008
2.4.3
Table 83:

LD0.T1PTTR1 Thermal overload values (1)

Object type
Addr
20
10142
20
10143
21
10144
21
10145
2.4.4
Table 84:

LD0.DARREC1 Autorecloser (1)

Object type
Addr
21
10103
21
10104
2.4.5
Table 85:

LD0.SECRSYN1 Synchrocheck (1)

Object type
Addr
21
10163
40
IEC 61850 name
SA name
.FltNum.stVal
-
.MemUsed.stVal
-
LD0.LPHD1
.PhyHealth.stVal
.PhyHealth1.stVal
.PhyHealth2.stVal
.NumCmpChg
.NumPwrUps.stVal
.WrmStr.stVal
.WacTrg.stVal
LD0.T1PTTR1 Thermal overload values (1)
IEC 61850 name
SA name
LD0.T1PTTR1
.Tmp.mag
TEMP
.TmpRI.mag
TEMP_RL
.TmmsOp.stVal
THERMLEV_ST
.TmmsRecEna.stVal
THERMLEV_END
LD0.DARREC1 Autorecloser (1)
IEC 61850 name
SA name
LD0.DARREC1
.AutoRecSt.stVal
STATUS
.ShotPntr.stVal
SHOT_PTR
LD0.SECRSYN1 Synchrocheck (1)
IEC 61850 name
SA name
LD0.SECRSYN1
.EnSt.stVal
ENERG_STATE
Description
Number of DR recordings
DR Rec. memory used
Device Health
Warning
Internal fault
Num of comp changes
Num of power ups
Num of warm starts
Num of wdog starts
Description
Object temperature
Relative temperature
Est. time to operate
Est. time to deactivate block
Description
Autorec. status
Shot pointer value
Description
Energ. state of line and bus
Recloser Protection and Control RER615
1MRS757824 C
Values
0...65535
0...100 [%]
0=OK; 1=Warn; 2=Error
See the technical
manual.
See the technical
manual.
0...999999
0...999999
0...999999
0...999999
Values
-100.0...9999.9 [C]
0.00...99.99 [C]
0...600.000 [ms]
0...600.000 [ms]
Values
-2...4
0...65535
Values
0...4
See the technical
manual.
Point List Manual