Section 2
IEC 60850-5-101/104 data mappings
Object type
Addr
1
1051
1
1052
1
1053
1
1054
2.3.30
Table 32:
LD0.PHPTUV3 Phase undervoltage protection (3)
Object type
Addr
1
1063
1
1064
1
1065
1
1066
1
1059
1
1060
1
1061
1
1062
2.3.31
Table 33:
LD0.PHPTOV1 Phase overvoltage protection (1)
Object type
Addr
1
1023
1
1024
1
1025
1
1026
1
1019
1
1020
1
1021
1
1022
24
IEC 61850 name
SA name
.Op.general
OPERATE
.Op.phsA
.Op.phsB
.Op.phsC
LD0.PHPTUV3 Phase undervoltage protection (3)
IEC 61850 name
SA name
LD0.PHPTUV3
.Str.general
START
.Str.phsA
.Str.phsB
.Str.phsC
.Op.general
OPERATE
.Op.phsA
.Op.phsB
.Op.phsC
LD0.PHPTOV1 Phase overvoltage protection (1)
IEC 61850 name
SA name
LD0.PHPTOV1
.Str.general
START
.Str.phsA
.Str.phsB
.Str.phsC
.Op.general
OPERATE
.Op.phsA
.Op.phsB
.Op.phsC
Description
General operate
phase A operate
phase B operate
phase C operate
Description
General start
phase A start
phase B start
phase C start
General operate
phase A operate
phase B operate
phase C operate
Description
General start
phase A start
phase B start
phase C start
General operate
phase A operate
phase B operate
phase C operate
Recloser Protection and Control RER615
1MRS757824 C
Values
1=Operate
1=Operate
1=Operate
1=Operate
Values
1=Start
1=Start
1=Start
1=Start
1=Operate
1=Operate
1=Operate
1=Operate
Values
1=Start
1=Start
1=Start
1=Start
1=Operate
1=Operate
1=Operate
1=Operate
Point List Manual