The Report IP Service must be enabled as the primary communication channel, the Service Mode must
be configured to start with the operating system, and the Reporting Protocol must be set to ArmorIP.
-
Refer to the section
-
The Trouble Area must be armed. Refer to the section
Operator Reference Manual.
In the ArmorIP Internet Monitoring Software the Poll Time must be set to 40 seconds and the Grace Time
must be set to 20 seconds. Refer to the section
Monitoring Application User Manual.
Central Station Signal Receiver
The maximum number of signal transmitting units connected to any transmission channel shall conform to
the manufacturer's recommendations. The ArmorIP Receiver supports up to 10000 simultaneous
connections.
Refer to the section
Internet Connections Requirements
further details.
Number of attempts
In the event of unsuccessful communication, a digital alarm communicator transmitter shall make a minimum
of 5 and a maximum of 10 attempts. Where the maximum number of attempts to complete the sequence is
reached, an indication of the failure shall be made at the premises.
In the Protege system, the reporting service selected as Contact ID must have the number of attempts
programmed to 5 attempts. The Dialing Attempts option must be programmed. Refer to the section
Contact ID | Settings
Check-In Time
DACT communication channel check-in time is not to exceed 24 hrs.
Trouble Input Service Test Report
-
The Test Report Time must be programmed. Refer to the section
Operator Reference Manual.
-
The Generate Input Restore on Test Input option must be enabled. Refer to the section
Options
in the Operator Reference Manual.
-
The Test Report Time is Periodic option must be enabled. Refer to the section
the Operator Reference Manual.
Ethernet Connections
All ethernet network connections shall be installed within the same room as the equipment.
External Wiring
All wiring extending outside of the enclosure must be protected by conduit.
Power Supply Mains Power Connection
If a flexible cord is used to connect to line voltage, strain relief must be provided for the cord inside the
enclosure or at the knockout.
The power supply is not intended to be mounted on the exterior of vault, safe, or stockroom.
Arming Signal
A bell or visual indicator used as an arming acknowledgment signal must be listed to a ULC security,
signaling or fire standard. If intended to be mounted outside, it must be rated for outdoor use.
Keypad Wiring
The RS-485 connection to the keypad must be wired such that the shorts and other faults on the RS-485 line
connection of the keypad will not cause the controller to malfunction.
Fire Areas
Fire areas shall be separated from burglar areas through area partitioning.
NOTE:
Any available dry relay contact on the Protege controller or output expander may be used for the
FACP system, provided the selected output is programmed as the Report OK output.
PRT-ZX16-DIN | Protege DIN Rail 16 Input Expander | Installation Manual
Report IP
in the Operator Reference Manual.
in the Operator Reference Manual.
Trouble Inputs | Areas and Input Types
Poll/Grace Time
in the ArmorIP Version 3 Internet
in the ArmorIP Receiver Installation Manual for
Controllers | Configuration
in the
in the
Controller |
Controller | Options
in