installation

FLUEING ARRANGEMENT FOR VERTICAL TERMINATIONS

Vertical Flueing with One(1) 90
The shaded area in the diagram shows all allowable combinations
of straight vertical and offset to vertical terminations, using two
45
elbow, with Rigid Pipe Flueing Systems.
o
Flue must be supported at offsets.
Maintain clearances to combustibles as listed in the
"Clearances" section.
Horizontal flue must be supported every 3 feet.
Firestops are required at each floor level and whenever
passing through a wall.
Must use optional rigid pipe adaptor (Part# 510-994) when
using rigid pipe flue systems.
Refer to the "Flue Restrictor Position" section for details on
how to change the flue restrictor from the factory setting of
Set 0 to Set 1 or Set 2 if required.
"THIS UNIT MUST ALWAYS
TERMINATE / FLUE
DIRECTLY TO THE OUTDOORS."
30
Elbows (1 - 90
2 - 45
o
o =
)
o
N
OTE: Restrictor settings
Propane: Set #2 - 18mm
ULPG: Set#1 - 26mm
Restrictor Set #3
15mm open
Regency GF900C-2 Gas Fireplace