16.5 EKVDX option
VAM350~2000J8VEB
Heat reclaim ventilation unit
4P664012-1 – 2021.08
Zone control system
1
c
a
2
c
a
a Controller
b Heat reclaim ventilation unit (VAM)
c Air conditioner
d Central controller
1
Zone 1
2
Zone 2
▪
Use of the central controller enables zone control via the central control line (up
to 64 zones).
▪
Central controller DCS302C(A)51, intelligent Touch Controller DCS601C51, or
intelligent Touch Manager DCM601A51.
▪
A central controller can control independent operation of the VAM in each zone.
For configuration, see
"17.3.6 Central control
VAM and EKVDX combinations have the following restrictions:
▪
One remote controller per VAM and EKVDX combination.
▪
NO group control.
▪
NO slave remote controllers.
▪
NO linkage to indoor(s) other than the one towards EKVDX.
▪
NO direct duct to indoor(s) other than the one towards EKVDX.
▪
NO supervising remote control connected on EKVDX. It has to be installed on
normal VRV indoor.
See the EKVDX installer and user reference guide for more information.
Independent system with EKVDX
c
a
c
a
c
a
a Controller
b Heat reclaim ventilation unit (VAM)
c EKVDX unit
b
a
d
b
system" [
b
b
b
16
System configuration
|
4
78].
Installer and user reference guide
67