IBM 9306 Hardware Maintenance Manual page 153

Hide thumbs Also See for 9306:
Table of Contents

Advertisement

Rack PDU specifications
When connected to a dedicated power source, the Rack PDU conforms to UL950,
CSA 22.0-950, EN-60950, and IEC-950 standards. The following table contains the
product specifications for the Rack PDU:
Height
Width
Depth
Weight
Operating temperatures
Operating humidity
Rated voltage
Rated frequency
Maximum power rating
Circuit breaker
Power inlet
Power outlets
43 mm (1.7 in.)
192 mm (7.5 in.)
221 mm (8.7 in.)
1.5 kg (3.2 lbs)
10°C–35°C (50°F–95°F) at 0–914 m (0–3000 ft)
10°C–32 °C (50°F–90°F°) at 914–2133 m (3000–7000 ft)
8–80% (non-condensing)
100–240 V ac, 15 A, single-phase
50–60 Hz
3600 VA
Two-pole, 15 A with time-delay protection for up to 600 A
input current without nuisance tripping.
IEC 320-C20 inlet rated at 16 A (VDE) / 20 A (UL/CSA)
Seven IEC 320-C13 outlets rated at 10 A (VDE) / 15 A
(UL/CSA)