Service Alarms Settings; Run Hours Reset (For Service Alarms) - RefPlus Guardian+ RC-A Programming Manual

Opti-mist plus adiabatic control
Table of Contents

Advertisement

NOTE: The Pump Oil parameter is only shown when the system uses a Modulating Pump.
The controller saves the operating time for devices that are subject to maintenance (time since last maintenance was
performed). The second of the main screens shows the counters. Once a counter reaches the time set here, a service alarm
is triggered.
Minimum off: When a service alarm is triggered, you can reset the alarm to stop the buzzer and turn off the alarm light. The
alarm will not be triggered again during the time set here, to allow the user to service the system. When the maintenance is
done, reset the counter, as shown in steps 26 to 27. Note: Service alarms will not stop the adiabatic system.
19. Press
to move cursor to a specific device.
20. Use
to define an operating time for the device.
21. Press
to confirm your selection.
22. Repeat steps 19 to 21 for other devices.
23. Press
to move cursor to the parameter Minimum off.
24. Use
to set the desired value and press
25. Press
, the display will read:
26. Press
and use
27. Press
to clear the run hours counter.
28. Repeat steps 26 to 27 to clear other devices run hours.
R
SERVICE ALARMS TIME:
Pump oil:
UV lights:
Filter:
Demineralizer: 00600hrs
Minimum off:
to confirm your selection.
RUN HOURS RESET
This will reset the
RUN HOURS since last
maintenance.
Choose device
to select a specific device.
02000hrs
08000hrs
00600hrs
072hrs
29