Delays - RefPlus Guardian+ RC-A Programming Manual

Opti-mist plus adiabatic control
Table of Contents

Advertisement

56. Use
to set Delay and press
57. Press
, the display will show the Digital Input B6 screen:
Digital input B6 (Water pump discharge switch, B6): signal from a high-pressure switch reading the pump outlet. If the
input is active, after the delay shown here, an alarm is raised and the system stops. This input is used on systems with a
Modulating Pump. Note: Analog input 6 converted by software to digital input.
58. Press
and use
59. Press
to confirm your selection.
60. Use
to set "Active if" to OPEN or CLOSED and press
Example: If when pump outlet pressure is normal, the status is CLOSED, then set the "Active if" condition to OPEN. Then,
when pressure is abnormal (high), the contact will open and the controller will trigger an alarm and stop the system after the
delay shown here.
61. Use
to set Delay and press
62. Press
to return to the FACTORY SETUP MENU. The display will read:
63. Use
to select DELAYS.
64. Press
to confirm your selection. The display will read:
65. Press
.
66. Use
to enter the ON/OFF value. The ON/OFF value is the delay to start the adiabatic control once set to ON.
67. Press
to confirm your
to enter the Fact. pass. enab value.
68. Use
22
to confirm.
Digital Input B6
Water pump disch. sw.
Active if
CLOSED
Delay time= 03secs.
to set to Water pump disch. sw. (if installed).
to confirm.
FACTORY SETUP MENU
SYSTEM SPECIFICATIONS
DIGITAL INPUTS

DELAYS

DELAYS
ON/OFF:
Fact. pass. enab:
Drain if no dem:
Air vent valve: 030secs
Set 0.23S per feet of
5/8" pipe & 3.1 GPM.
selection.
Status
OPEN
to confirm.
015secs
10mins
0072hs
R