SETTING UP YOUR CONTROLLER USING THE PROGRAMMING MENU

Use the Programming menu to make the initial setup of your Guardian+ Adiabatic Controller or to modify a parameter. In this
section, you will enter parameters in the following sections:

1. FACTORY SETUP

2. USER SETUP
3. SERVICE SETUP
4. CLOCK
1. FACTORY SETUP
1. Enter the Programming menu by pressing
2. Use
to scroll the Programming menu and select D) FACTORY SETUP.
3. Press
. The display will read:
The screen may prompt you to enter the factory password. Please contact RefPlus to obtain your factory password.
4. Press
.
5. Use
to enter the factory password. Note: If password is not accepted, verify that date and time are set
properly. See page 30 for Clock Adjustment.
6. Press
to confirm the password. The display will read:
16
. The display will read:
PROGRAMMING MENU
G>VERSION INFO
A>UNIT ON/OFF
B>USER SETUP
ENTER FACTORY PASSWORD
0000
FACTORY SETUP MENU
ALARMS LOGGING RESET
SYSTEM SPECIFICATIONS
DIGITAL INPUTS
R