Advertisement

Cord Clamp
Wire Hole
Electrical Box
Component
Electrical Box
Cover
Transmission Wiring
Transmission Wiring
(between Indoor
Unit and Outdoor Unit)
Remote Control
Switch Cable
Earth Screw
Power Source Wiring
7.1
Screw A
Screw B
Screw B
P
Base Board(two-layer)
Power Source Wiring
(a) Remove electrical box cover (by loosening one
screw (A)).
(b)
Loosen two screws (B) on electrical box
component and pull out the component.
(c)
Fix the wire harness from connecting port to
electrical box with cord clamp to prevent it
from scratched by edge of container of other
component.
(d)
Mount a magnetic ring to the communication wire,
which shall be wound by three circles around the
wire and then fixed with cord clamp provided in the
accessory bag.
(e) Upon completion of wiring, mount electrical box,
and take care not to press any wire.
•After wire is connected to terminal board, be
sure to fix it with cord clamp and lay the wire in
cable tray to prevent it from being squeezed and
fire caused thereby.