Inverter-driven multi-split air conditioner(heat pump)

Advertisement

2or2.5
5.1
Ceiling
a
c
300)
(
50 )
P
Drain Hose
(Accessory)
2
Suspension
-
1 1.5m
Bracket
1/25 to 1/100
Down-Slope
(mm)
950mm.
P
Drain pipe must be installed horizontally or in upward slope
to prevent occurrence of air column, or otherwise water will
flow from rear of the equipment to cause leakage or
abnormal noise when the equipment is shut down.
(a) Use the drain pipe and hose clamp provided
by the manufacture.
(b) Do not impose too much force on the pipe
joint to prevent damage to it.
(c) Do not use any bent or twisted pipe, which
may cause leakage.
(d) Complete insert the drain pipe provided by
the manufacturer, or otherwise leakage may
be caused.
Hose Band(Accessory)
Tightening Torque 2.5~3.4(N.m)
Drain Pipe
Connection
20 + 5
Insert Drain Pipe Completely to
End of The Hose Connection
(Incorrect) Twisted and Incomplete Insertion
12
Drain Hose
Horizontal or Upward Slope
Drain Hose(Accessory)
Elbow or Polyvinyl Chloride VP25
No Adhesive Agent
Polyvinyl Chloride-based
to be
Adhesive Agent
(Correct)