Turn OFF the main power switch to the indoor
unit and the outdoor unit and wait for at least 3
minutes before electrical wiring work or a
periodical check is performed.
●
Check to ensure that the indoor fan and the
outdoor fan have stopped before electrical
wiring work or a periodical check is performed.
●
Protect the wires,drain pipe, electrical parts,
etc. from rats or other small animals.
If not protected, rats may gnaw at unprotected
parts and at the worst, a fire will occur.
●
Avoid any wire from contacting with
Refrigerant tube, edge of metal plate and
electrical part in the equipment, or otherwise
the wire may be damaged or even thereby
cause fire.
●
ELB with intermediate induction rate (with
shorter than 0.1 second or fewer) shall be
used, or otherwise electric shock or fire may
be caused.
●
Wire shall be fixed securely, since external
force imposed to the connecting terminal may
make it loose and thereby cause fire.
●
Do not use the power terminal strip used for
the air conditioner to sub-connect any power
cable, but use power branch box to sub-
connect power wire at indoor unit side instead,
and be sure to calculate wire capacity, or
otherwise too low capacity may cause fire.
●
The system shall not be started until all
inspections have been performed properly.
●
Wrap the accessory packing around the wires,
and plug the wiring connection hole with the
seal material to protect the product from any
condensate water or insects.
●
Tightly secure the wires with the cord clamp
inside the indoor unit.
●
Secure the cable of the remote control switch
using the cord clamp inside the electrical box.
●
Tighten screws according to the following
torque.
M4:1.0~1.3 N.m
M5:2.0~2.4 N.m
M6:4.0~5.0 N.m
M8:9.0~11.0 N.m
M10:18.0~23.0 N.m