Carrier OMNIZONE 50XJ064-104 Operating And Troubleshooting Manual

Carrier OMNIZONE 50XJ064-104 Operating And Troubleshooting Manual

Indoor self-contained remote air-cooled and water-cooled, vav systems 18 to 100 nominal tons

Advertisement

Quick Links

CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
MAJOR SYSTEM COMPONENTS . . . . . . . . . . . . . . . 1 -7
Comfort Controller Processor (PCB1) . . . . . . . . . . . . 1
Comfort Controller I/O Module (PCB2). . . . . . . . . . . . 2
Comfort Controller I/O Module (PCB3). . . . . . . . . . . . 2
Local Interface Display . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
PCB Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Control Module Communication. . . . . . . . . . . . . . . . . . 2
Carrier Comfort Network Interface. . . . . . . . . . . . . . . . 4
Accessory Sensors/Devices . . . . . . . . . . . . . . . . . . . 4
Wiring Control Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . 6
CONTROLS AND FUNCTIONS . . . . . . . . . . . . . . . . . 8-15
Using the Local Interface Display . . . . . . . . . . . . . . . . 8
Automatic Run Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Power Up the LID Display . . . . . . . . . . . . . . . . . . . . . . . 12
Log On to the LID Display . . . . . . . . . . . . . . . . . . . . . . . 12
Change the Default Password . . . . . . . . . . . . . . . . . . . 12
Set the Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Configure Schedules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Program Set Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Check System Parameters . . . . . . . . . . . . . . . . . . . . . . 14
Display Alarm History . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Set Controller Address . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Log Off from Controller . . . . . . . . . . . . . . . . . . . . . . . . . 15
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-26
Occupancy Determination. . . . . . . . . . . . . . . . . . . . . . . 16
Fan Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Sequence of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . 16
Diagnostic Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . 27-29
Run Test Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . 27
Alarm and Warning Lights . . . . . . . . . . . . . . . . . . . . 28
APPENDIX A - WIRING DIAGRAMS . . . . . . . . . 30-42
APPENDIX B - CONTROL SCREENS . . . . . . . . 43-64
Display Screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Configuration Screens . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Maintenance Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

SAFETY CONSIDERATIONS

Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components, and
equipment location. Only trained, qualified installers and
service mechanics should install, start up, and service this
equipment.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111
Catalog No. 535-00137
Book 1
1
Tab
2a 2b
Remote Air-Cooled and Water-Cooled, VAV Systems
Controls Operation and
Troubleshooting
Printed in U.S.A.
50BV020-064, 50XJ064-104
18 to 100 Nominal Tons
When working on this equipment, observe precautions in
the literature; on tags, stickers, and labels attached to the equip-
ment, and any other safety precautions that apply. Follow all
safety codes. Wear safety glasses and work gloves. Use care in
handling, rigging, and setting this equipment, and in handling
all electrical components.
Electrical shock can cause personal injury and death.
Shut off all power to this equipment during installation
and service. There may be more than one disconnect
switch. Tag all disconnect locations to alert others not to
restore power until work is completed.
This unit uses a microprocessor-based electronic control
system. Do not use jumpers or other tools to short out
components, or to bypass or otherwise depart from rec-
ommended procedures. Any short-to-ground of the con-
trol board or accompanying wiring may destroy the
electronic modules or electrical components.

GENERAL

This publication contains Start-Up, Controls Operation, and
Troubleshooting information for the 50BV,XJ units. These
OMNIZONE™ packaged units are self-contained, water-
cooled or remote air-cooled indoor units for use in VAV
(variable air volume) applications. Units are equipped with
Comfort Controller 6400 (CC6400) system controls. Refer to
the unit Installation Instructions for unit layout.

MAJOR SYSTEM COMPONENTS

Comfort Controller Processor (PCB1) -

The central processing unit for the OMNIZONE system
control is the Comfort Controller 6400. The Comfort Control-
ler provides general purpose HVAC (heating, ventilation and
air conditioning) control and monitoring capability in a stand-
alone or
network environment using closed-loop, direct dig-
ital control. The Comfort Controller 6400 has been pre-pro-
grammed to work in either stand-alone or CCN (Carrier Com-
fort Network) system installations.
The CC6400 processor is designed to provide heating and
cooling control, loop control, scheduling, and custom program-
ming. The main processor provides 16 field points (8 input and
8 output). Additional points are provided by the I/O modules
described on page 2. Table 1 lists the control inputs and outputs
for all CC6400 modules.
Specifications for the Comfort Controller 6400 may be
found in the Comfort Controller literature.
Form 50BV,XJ-2T
Pg 1
OMNIZONE™
Indoor Self-Contained
2-04
Replaces: 50BV,XJ-1T

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the OMNIZONE 50XJ064-104 and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier OMNIZONE 50XJ064-104

  • Page 1: Table Of Contents

    Control Module Communication....2 Carrier Comfort Network Interface....4 Optional and Field-Installed Accessory Sensors/Devices .
  • Page 2: Comfort Controller I/O Module (Pcb2)

    Comfort Controller I/O Module (PCB2) — input/output module is factory installed in the 50XJ unit and allows additional field points (8 inputs and 8 outputs): VFD (variable frequency drive) Bypass, VAV Terminals Control, Building Ventilation, and Heating Interlock. Comfort Controller I/O Module (PCB3) — accessory control input/output module can be ordered separate- ly and field-installed in the 50XJ unit.
  • Page 3 DESCRIPTION ABBREV. Inputs Main Controller (PCB1) Supply Air Temperature VFD Duct Static Pressure COL/Safeties — CMP MUX (Comprs.Status; Resister Bd.) Fire Alarm/Shutdown Condenser Waterflow Switch CDWF Remote Occupancy RMTOCC Duct High Static Limit Switch Entering Water Temp. Sensor I/O Board (PCB2) Mixed/Return Air Sensor MAT/RAT Filter Status Switch...
  • Page 4: Carrier Comfort Network Interface

    Fig. 1 — CC6400 Control Module LEDs Carrier Comfort Network Interface — units can be connected to the CCN (Carrier Comfort Network) if desired. System elements are connected to the communica- tion bus in a daisy chain arrangement. The negative pin of each system element’s communication connector must be...
  • Page 5 This signal is activated whenever the unit is in the occupied mode. SPACE TEMPERATURE SENSOR (50XJ PCB2) — A field- supplied Carrier space temperature sensor is required to maintain space temperature in sensor mode. SUPPLY AIR RESET (50XJ PCB2) — Supply air temperature set point may be reset using either the SPT or MA_RA.
  • Page 6: Wiring Control Devices

    OUTDOOR AIR TEMPERATURE SENSOR (50XJ PCB3) — This sensor is used to monitor outdoor air and broadcast the value over the Carrier Comfort Network (CCN). STAGE HEAT RELAYS (50XJ PCB3) — These relays con- trol up to four stages of electric heat, or other heating methods.
  • Page 7 AIR TERMINALS AND FRESH AIR DAMPER (50XJ PCB2) — The VAV Terminal Open (TRMOP), Ventilation Output (VENTR), VAV Terminals Control (TRMCT), and Heat Interlock Relay (HIR) terminals provide dry contacts to command the VAV terminals open; a ventilation damper open; VAV terminals to control to their cooling set points;...
  • Page 8: Controls And Functions

    CONTROLS AND FUNCTIONS Using the Local Interface Display — Interface Device (LID) is a CCN operator interface that gives the user the capability to view and modify all configuration and service data for the CC6400 control system. The LID also allows the user to override all point display and maintenance data.
  • Page 9 • Pressing the appropriate LID numeric key (i.e., 2) and the appropriate function key (i.e., access an item without having to scroll through all the items in that category. Press ENTER maintenance decision. Edit Mode — Because the LID first displays items in Status mode when it is powered up, the user must log on to the con- nected CC6400 Controller and press the switch to Edit mode.
  • Page 10: Automatic Run Test

    NUM. Algorithms Status (ALGO) (STAT) AO—Adaptive Control Hardware Points AO—Cooling CV Software Points AO—Cooling VAV Temperature Input AO—Fan Tracking Milliamp Input AO—Heating CV Custom Milliamp Input AO—Heating VAV Voltage Input AO—Humidity Control Custom Voltage Input AO—Mixed Air CV w/IAQ Sensed Discrete Input AO—Mixed Air VAV w/IAQ Latched Discrete Input AO—Permissive Interlock...
  • Page 11 2. Press 3 and then . The LID display will show: Controller Password 3. Press . The LID display will show: ENTER Log in to Controller Enter Password NOTE: The LID display has two modes: Edit mode and Status/Maintenance mode. If the LID display is in Edit mode, then the display will only show the word “pass- word.”...
  • Page 12: Power Up The Lid Display

    22. The control forces CMP4 (compressor 4) on, if config- ured, then waits 5 seconds. The LID display shows: Factory/Field Test Stop The yellow LED will go off, and the red LED will go off. 23. The control forces CMP4 off. 24.
  • Page 13: Configure Schedules

    8. Enter the last two digits of the current year. Press then press . The LID display will show: ENTER Update Clock 9. Press 1 and then to cause the controller to ENTER update the clock. The LID display will flash. Press CLEAR twice to view the default display and the clock should update to the input time and date.
  • Page 14: Check System Parameters

    Table 7 — Controller Set Points DESCRIPTION DISPLAY VALUE UNITS STATUS FORCE SCREENS OMNIZONE::SETPT01: Supply fan Status Occupied Lo Setpoint 0.3 in H2O Occupied Hi Setpoint 0.4 in H2O Unoccupied Lo Setpoint 0.3 in H2O Unoccupied Hi Setpoint 0.4 in H2O OMNIZONE::SETPT02: VAVRESETbaseline Occupied Lo Setpoint...
  • Page 15: Set Controller Address

    Table 8 — Controller Hardware Points DESCRIPTION DISPLAY VALUE UNITS STATUS FORCE NAME SCREENS OMNIZONE::HWP01-32: Hardware points Table 1 Supply Air Temperature Duct Static Pressure in H2O Comp. Status MUX 1.86 Volts Fire Alarm/ShutDown Enable Cond. Water Flow Switch Remote Occupancy Disable Duct High Press.
  • Page 16: Operation

    CC6400 schedule or ROCC point to function the Local/ Off/Remote switch must be set to Remote. When the OMNIZONE unit is connected to a Carrier Comfort Network and the Local/Off/Remote switch is set to Remote, the controller occupancy can be determined by a Network Group schedule, a Network Global schedule, or via Linkage from a linkage device such as a ComfortID™...
  • Page 17 COMRES triggers the compressor staging routine that controls the number of compressors energized. Units are equipped with 4 compressors piped in separate refrigerant circuits, and staged On/Off in a fixed sequential manner (compressor no. 1 through compressor no. 4). The compressor control routine uses a PID calculation to determine the percent- age of cooling required, from 1 to 100%.
  • Page 18: Diagnostic Features

    VAV TERMINAL OPERATION OUTPUT (50XJ) — The VAV terminal control output (TRMCT) closes a set of relay contacts to indicate to non-Carrier air terminals that the fan is either forced on or is going to turn on. This signals the terminals to open and start controlling to the desired CFM and Temperature set points.
  • Page 19: 50Xj Variable Frequency Drive Control

    LOW-PRESSURE SWITCH (LPS) — The Low-Pressure Switch is located in the suction refrigerant line of each compressor, and is set to open at pressures below 27 psig. It is wired in the 115 vac control power line of the compressor contactor (in series with the HPS and EFS), and activates the COL board (above) when it opens.
  • Page 20 STATUS MONITOR MODE — In Status Monitor mode, it is possible to monitor the VFD status (frequency command, output voltage, current, terminal information, etc.). Status monitor mode is entered by pressing the Setup/Program/Monitor key, then selecting MON at the mode selection menu and pressing the Read/Write key.
  • Page 21: Led Message

    Table 13 — VFD Trip Messages for 50XJ Unit LED MESSAGE nErr Displayed in the trip history in standard monitor mode when no trip has been recorded since the last VFD reset or trip clear. Overcurrent during acceleration trip Overcurrent during deceleration trip Overcurrent during normal (constant speed) run trip OC1P Overcurrent in DC section during acceleration trip...
  • Page 22: 50Bv Variable Frequency Drive Control

    Table 14 — VFD Mode Summary for 50XJ Unit KEY OPERATON — S/P/M S/P/M S/P/M DOWN DOWN DOWN DOWN DOWN DOWN DOWN DOWN DOWN DOWN DOWN DOWN DOWN 50BV Variable Frequency Drive Control — variable frequency drive is factory wired and programmed for proper operation with the unit controls;...
  • Page 23 VEC lamp RUN lamp Lights when the inverter is Lights when sensorless operating. Blinks when the vector operation control automatic acceleration/deceleration is running. is operating ECN lamp Lights whenenergy-saving mode is in operation. Charge Lamp CHARGE Indicates that high voltage is still present within the inverter.
  • Page 24 • Increase the acceleration time ACC. • Check the V/F parameter. • Use F301 (auto-restart) and F302 (ride-through control). • Increase the carrier frequency F300. • Increase the deceleration time dEC. • Reduce the load fluctuation. • Check the load (operated machine).
  • Page 25 Table 16 — Trip Messages for 50BV VFD (cont) ERROR COMMUNICATION PROBLEM CODE Overvoltage during constant-speed operation Inverter overload Motor overload *EPHO Output phase failure *EPH1 Input phase failure External thermal trip • A thermal trip command is entered from Over-torque trip Dynamic braking resistor overload trip...
  • Page 26: Operation

    Table 16 — Trip Messages for 50BV VFD (cont) ERROR COMMUNICATION PROBLEM CODE Small-current operation trip Ground fault trip Emergency stop Err2 Main unit RAM fault Err3 Main unit ROM fault Err4 CPU fault trip Err5 Remote control error EtYP Inverter type error EEP1 EEPROM fault...
  • Page 27: Troubleshooting

    Refer to Tables 17-21 for troubleshooting information. Run Test Troubleshooting — The automatic run test is a diagnostic tool used during unit start-up. Table 17 describes troubleshooting specifically for the automated run test. PROBLEM Control modules do not have lights when unit power on. Control display does not light up when unit power on.
  • Page 28: Standard Diagnostic Features, Alarm And Warning Lights

    FUNCTION ALARM MESSAGE (Actual Text) SAT xx.x dF outside limit of xxx.x dF Duct Static Sensor Failure DSP_ALM Fire Shutdown Duct High Static Pressure CSMUX x.xx Volts outside CSMUX limit of x.xx Volts Check Condenser Water Flow CDWF Change Filters FLTS Economizer Freeze Condition FREEZ...
  • Page 29 Table 21 — Compressor MUX Board Voltages COMP VOLTS None 1.86 1.50 < V < .95 2.88 last val < = V < 2.95 3.59 last val < = V < 3.68 4.44 last val < = V < 4.55 5.13 last val <...
  • Page 30: Appendix A - Wiring Diagrams

    APPENDIX A — WIRING DIAGRAMS VFD2 COMMON VFD1 24VAC CSMUX...
  • Page 32 ECONO MBV 24VAC VFD2 Close Open COMMON VFD1 24VAC CSMUX...
  • Page 35 VFD2 COMMON VFD1 24VAC CSMUX...
  • Page 36 VFD2 COMMON VFD1 24VAC CSMUX...
  • Page 37 LEGEND AND NOTES FOR ALL 50BV WIRING DIAGRAMS ALARM — Unit Alarm Relay (Critical Fault) ALM-CM — Alarm/Warning Relay Common — Analog Output AQUA — Aquastat — Blower Motor BPS_S — Fan Start/Stop Relay (VFD Bypass Mode) — Blower Relay BYPAS —...
  • Page 38 LOW VOLTAGE CONTROL WIRING PCB1 503/BRN 502/RED 510/WHT 512/YEL 592/BRN 514/BLK 515/WHT 516/GRA 1 2 3 4 5 6 7 8 529/YEL 1 2 3 4 5 6 7 8 532/PNK 1 2 3 4 5 6 7 8 4-20mA OTHER 612/BLU 1 2 3 4 5 6 7 8...
  • Page 39 Bussman MDQ5 115 V 5 A, 250 V FU27 HRN1 CMP1 HRN1 LPS1 HPS1 CMP2 HRN1 LPS2 HPS2 HRN2 CMP3 HRN2 HPS3 LPS3 CMP4 HRN2 LPS4 HPS4 BPS_S* DS1* 115 V HRN1 OLR1 FRZ1 OLR2 FRZ2 HRN2 OLR3 FRZ3 OLR4 FRZ4 BYPAS* NOTE 1...
  • Page 40: Power Wiring

    USE COPPER SUPPLY WIRES. DISC1* 206/BLK 100/BLK 207/BLK 101/BLK 208/BLK 102/BLK Phase rotation sequence is ABC (L1-L2-L3). FUSES 1-18 ARE 600 V, CLASS RK-5 FUSES. FUSES 25-26 ARE 600 V, CLASS CC FUSES. FUSE USAGE 15 HP 20 HP 25 HP FU1-3 30 HP 40 HP...
  • Page 41 PCB3 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 4-20 mA OTHER 1 2 3 4 5 6 7 8 0-10 VDC 4-20 mA 50BV,XJ Accessory Control Module (PCB3) Schematic DEHUM TOWER...
  • Page 42 LEGEND AND NOTES FOR ALL 50XJ WIRING DIAGRAMS ALARM — Unit Alarm Relay (Critical Fault) ALM-CM — Alarm/Warning Relay Common BPS_S — Fan Start/Stop Relay (VFD Bypass Mode) BYPAS — VFD Bypass Control — Compressor Contactor — Circuit Breaker CDWF —...
  • Page 43: Appendix B - Control Screens

    DESCRIPTION OMNIZONE::HWP01-32:Hardware points Table 1 Supply Air Temperature Duct Static Pressure Comp. Status MUX Fire Alarm/Shut Down Cond. Water Flow Switch Remote Occupancy Duct High Press. Switch Entering Water Temp. Compressor 1 Relay Compressor 2 Relay Compressor 3 Relay Compressor 4 Relay Supply Fan/VFD VFD Speed Signal Non Critical Fault...
  • Page 44 DESCRIPTION OMNIZONE:Custom Configuration Compressor Stages Reset Ratio CDWF 0=NO,1=YES ECON 0=NO,1=YES EWT Reset 0=NO,1=YES MOD.VLV 0=NO,1=YES 0=CONST.,1=VARIABLE 0=RAT,1=MAT,2=NONE PHASE 0=NO,1=YES FREEZ 0=NO,1=YES ENABLE ECON. SPT 0=NO,1=YES PRES 0=NO,1=YES TWR 0=NO,1=YES LWT 0=NO,1=YES IAQ 0=NO,1=YES IRH 0=NO,1=YES BSP 0=NO,1=YES BSP Range BSP LOW VALUE Setpoints OMNIZONE::SETPT01: Supply fan Status...
  • Page 45: Configuration Screens

    DESCRIPTION OMNIZONE::CC6400:Controller Identification Description: Location: Software Part Number: Model Number: Serial Number: Reference Number: OMNIZONE::ADAPT01: VAVRESET Software point con- trol Analog Output Point Status Point Time Schedule Setpoint Schedule Reset Point Reset Start Reset Value Stop Reset Value Control Point PID_Master_Loop Proportional Gain Integral Gain...
  • Page 46 DESCRIPTION OMNIZONE::DOPI_01: Supply Fan Status Discrete Output Point Time Schedule Setpoint Schedule Permissive Interlock Control Point Type Occ Discrete State Unocc Discrete State Occ Analog Test Unocc Analog Test Override Value Hysteresis Persistence Time Analog Control Point Discrete Control Point Power on Delay OMNIZONE::ANCTL02: Humidity Control Discrete Output Point...
  • Page 47 DESCRIPTION OMNIZONE::PRES: Head Pressure(Comp1) Low Input Endpoint High Input Endpoint Low Conversion Endpoint High Conversion Endpoint Low Input Fault High Input Fault OMNIZONE::RESET: Ext. Supply Air Reset Low Input Endpoint High Input Endpoint Low Conversion Endpoint High Conversion Endpoint Low Input Fault High Input Fault OMNIZONE::ALARM: Critical Fault Output Logic Type...
  • Page 48 DESCRIPTION OMNIZONE::HIR: Heat Interlock Relay Output Logic Type Minimum Off Time Minimum On Time Delay Time OMNIZONE::PUMP: Pump Request Output Logic Type Minimum Off Time Minimum On Time Delay Time OMNIZONE::SF: Supply Fan/VFD Output Logic Type Minimum Off Time Minimum On Time Delay Time OMNIZONE::TOWER: Cooling Tower Request Output Logic Type...
  • Page 49 DESCRIPTION OMNIZONE::DSALM02: Phase Protection Monitored Input Point Comparison Point Alarm Inhibit Point Discrete Check Alarm Logic Enable Delay Time Persistence Time Alarm Processor Alarm Processing Re-Alarm Interval Alarm=1 or Alert=0 Alarm Level Alarm Source Alarm Routing Alarm Description Index Alarm Message - Part 1 Alarm Message - Part 2 Alarm Message - Part 3 Alarm Message - Part 4...
  • Page 50 DESCRIPTION OMNIZONE::DSALM05: Fire alarm Monitored Input Point Comparison Point Alarm Inhibit Point Discrete Check Alarm Logic Enable Delay Time Persistence Time Alarm Processor Alarm Processing Re-Alarm Interval Alarm=1 or Alert=0 Alarm Level Alarm Source Alarm Routing Alarm Description Index Alarm Message - Part 1 Alarm Message - Part 2 Alarm Message - Part 3 Alarm Message - Part 4...
  • Page 51 DESCRIPTION OMNIZONE::DSALM08: Compressor 1 Alarm Monitored Input Point Comparison Point Alarm Inhibit Point Discrete Check Alarm Logic Enable Delay Time Persistence Time Alarm Processor Alarm Processing Re-Alarm Interval Alarm=1 or Alert=0 Alarm Level Alarm Source Alarm Routing Alarm Description Index Alarm Message - Part 1 Alarm Message - Part 2 Alarm Message - Part 3...
  • Page 52 DESCRIPTION OMNIZONE::DSALM11: Compressor 4 Alarm Monitored Input Point Comparison Point Alarm Inhibit Point Discrete Check Alarm Logic Enable Delay Time Persistence Time Alarm Processor Alarm Processing Re-Alarm Interval Alarm=1 or Alert=0 Alarm Level Alarm Source Alarm Routing Alarm Description Index Alarm Message - Part 1 Alarm Message - Part 2 Alarm Message - Part 3...
  • Page 53 DESCRIPTION OMNIZONE::EHVAV01: DO - Elec Heat VAV 01 Discrete Output Point 1 Discrete Output Point 2 Discrete Output Point 3 Discrete Output Point 4 Discrete Output Point 5 Discrete Output Point 6 Fan Status Point Sensor Group/SPT Sensor Time Schedule Setpoint Schedule High Humidity Switch Humidity Setpoint...
  • Page 54 DESCRIPTION OMNIZONE::INTLK02: Ok to Cool Discrete Output Point Discrete Input Point 1 Discrete Input Point 2 Discrete Interlock Input 1 Comparison Input 2 Comparison Off Persistence Time On Persistence Time Output Logic Type Power on Delay OMNIZONE::INTLK03: OK Fan + Sup. Fan Stat Discrete Output Point Discrete Input Point 1 Discrete Input Point 2...
  • Page 55 DESCRIPTION OMNIZONE::INTLK09: Condenser Pump Discrete Output Point Discrete Input Point 1 Discrete Input Point 2 Discrete Interlock Input 1 Comparison Input 2 Comparison Off Persistence Time On Persistence Time Output Logic Type Power on Delay OMNIZONE::INTLK10: Tower Request Discrete Output Point Discrete Input Point 1 Discrete Input Point 2 Discrete Interlock...
  • Page 56 DESCRIPTION OMNIZONE::LMALM02: Entering WaterTemp. Monitored Input Point Alarm Inhibit Point Limit Check Low Limit High Limit Enable Delay Time Persistence Time Hysteresis Alarm Processor Alarm Processing Re-Alarm Interval Alarm=1 or Alert=0 Alarm Level Alarm Source Alarm Routing Alarm Description Index Alarm Message - Part 1 Alarm Message - Part 2 Alarm Message - Part 3...
  • Page 57 DESCRIPTION OMNIZONE::OCCPC01: Occupancy 01 Time Schedule Manual Override Hours Period 1: Day of Week Period 1: Occupied from Period 1: Occupied to Period 2: Day of Week Period 2: Occupied from Period 2: Occupied to Period 3: Day of Week Period 3: Occupied from Period 3: Occupied to Period 4: Day of Week...
  • Page 58: Maintenance Screens

    DESCRIPTION OMNIZONE::VPTESTC: Field Test Field Test Reschedule Rate Power on Delay OMNIZONE::MODECTRC: Mode Control Determines Heat Reschedule Rate Power on Delay Run Fan in Bypass Reschedule Rate Power on Delay Water Economizer Control Reschedule Rate Power on Delay Mod Valve & Econo Reschedule Rate Power on Delay OMNIZONE::SETSYNCC: Setpoint Synchronization...
  • Page 59 DESCRIPTION OMNIZONE::ANCTL01: Supply Fan Status Discrete Output Point Sensor Group/SPT Sensor Occupied ? Analog Low Setpoint Lo Setpoint + Hyst Hi Setpoint - Hyst High Setpoint Reference Output Task Timer OMNIZONE::ANCTL02: Humidity Control Discrete Output Point Sensor Group/SPT Sensor Occupied ? Analog Low Setpoint Lo Setpoint + Hyst...
  • Page 60 DESCRIPTION OMNIZONE::PRES: Head Pressure(Comp1) System Value Force Status Alarm Status Sensor Value Hardware Value Channel Number Control Algorithm Name Alarm Algorithm Name OMNIZONE::RESET: Ext. Supply Air Reset System Value Force Status Alarm Status Sensor Value Hardware Value Channel Number Control Algorithm Name Alarm Algorithm Name OMNIZONE::UPDATEDB: Database Control Database Error...
  • Page 61 DESCRIPTION OMNIZONE::DXVAV01: Compressor Staging Discrete Output Point 1 Discrete Output Point 2 Discrete Output Point 3 Discrete Output Point 4 Discrete Output Point 5 Discrete Output Point 6 Fan Status Point Sensor Group/SPT Sensor Occupied ? High Humidity Switch High Humidity Setpoint High Humidity Sensor VAV Setpoint Reset Setpoint...
  • Page 62 DESCRIPTION OMNI ZONE::HCVAV01: AO - Heating VAV 01 Heating Coil Valve Fan Status Point Sensor Group/SPT Sensor Occupied ? Space Setpoint High Humidity Switch High Humidity Setpoint High Humidity Sensor Morning Warm Up Reference Output Morning Warmup ? PID_Master_Loop Reference Output Proportional Term Integral Term Derivative Term...
  • Page 63 DESCRIPTION OMNIZONE::LMALM01: Supply air Sensor (Typical Limit Alarm) Monitored Input Point Alarm Inhibit Point Limit Check Alarm Status Alarm Value Exceeded Limit Alarm Processor Alarm Type Time of Last Message Month of Last Message Day of Last Message Year of Last Message Task Timer OMNIZONE::DSP: Duct Static Pressure (Typical Milliamp Input) System Value...
  • Page 64 Execution Time Compressor Fault/Test Task State Task Timer Execution Time Copyright 2004 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 PC 111 Catalog No. 535-00137...

Table of Contents

Save PDF