Carrier Omnizone 50XCR06 Installation, Start-Up And Service Instructions Manual
Carrier Omnizone 50XCR06 Installation, Start-Up And Service Instructions Manual

Carrier Omnizone 50XCR06 Installation, Start-Up And Service Instructions Manual

Remote air-cooled indoor self-contained systems

Advertisement

CONTENTS
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-11
Step 2 - Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 7
Step 4 - Install Return-Air Ductwork . . . . . . . . . . . . 8
Step 5 - Check Return-Air Filters . . . . . . . . . . . . . . . 8
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-18
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Compressor Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Operating Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18,19
Cleaning Evaporator Coil . . . . . . . . . . . . . . . . . . . . . . . 18
Lubrication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Indoor Fan Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . 18
Pulley Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Belt Tension Adjustment . . . . . . . . . . . . . . . . . . . . . . . . 18
Changing Fan Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Fan Bearing Replacement . . . . . . . . . . . . . . . . . . . . . . . 18
Concentric Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
(after Lockout/Tagout) . . . . . . . . . . . . . . . . . . . . . . . . . . 19
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Checking System Charge . . . . . . . . . . . . . . . . . . . . . . . 20
Evaporator-Fan Motor Removal . . . . . . . . . . . . . . . . . 20
Pressure Relief Device . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Current Protection Device. . . . . . . . . . . . . . . . . . . . . . . 20
High and Low-Pressure Switches . . . . . . . . . . . . . . . 20
Oil Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 21-27
START-UP CHECKLIST . . . . . . . . . . . . . . . . . CL-1, CL-2

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air-conditioning com-
ponents and equipment can be dangerous. Only trained, quali-
fied installers and service mechanics should install, start-up,
and service this equipment.
When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the equip-
ment. Follow all safety codes. Wear safety glasses and work
gloves.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500193-01
Installation, Start-Up and
Service Instructions
Page
Printed in U.S.A.
Indoor Self-Contained Systems
.
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all discon-
nect locations to alert others not to restore power until work
is completed.
Use care in handling, rigging, and setting bulky equipment.
Personal injury could result.
DO NOT USE TORCH to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and gog-
gles and proceed as follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from sys-
tem using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen
and the work area should be well ventilated. Refrig-
erant in contact with an open flame produces toxic
gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit. Use a pan to catch
any oil that may come out of the lines and as a gage
for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when nec-
essary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal
injury or death.
DO NOT re-use compressor oil or any oil that has been
exposed to the atmosphere. Dispose of oil per local codes
and regulations. DO NOT leave refrigerant system open to
air any longer than the actual time required to service the
equipment. Seal circuits being serviced and charge with
dry nitrogen to prevent oil contamination when timely
repairs cannot be completed. Failure to follow these proce-
dures may result in damage to equipment.
Form 50XCR-6SI
Pg 1
Omnizone™
50XCR06-24
Remote Air-Cooled
WARNING
CAUTION
WARNING
CAUTION
1-18
Replaces: 50XCR-5SI

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Omnizone 50XCR06 and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier Omnizone 50XCR06

  • Page 1: Table Of Contents

    Omnizone™ 50XCR06-24 Remote Air-Cooled Indoor Self-Contained Systems Installation, Start-Up and Service Instructions CONTENTS WARNING Page SAFETY CONSIDERATIONS..... . 1 Electrical shock can cause personal injury and death. Shut GENERAL .
  • Page 2: General

    See Fig. 1-5 for unit dimensions and refer to Table 2 for unit GENERAL operating weights. Applicable installation codes may limit this Omnizone™ single package cooling units are designed to cabinet to installation only in a single-story residence. provide the flexibility required in replacement, renovation, and new construction.
  • Page 3 DISCH LIQUID DIAMETER DIAMETER COND EVAP EVAP RETURN DISCH LIQUID EVAP SUPPLY DUCT WIDTH HEIGHT DEPTH UNIT SWAGE SWAGE SECTION SECTION DUCT CONN CONN (Blower Opening) 50XCR (ID) (ID) 68.0 64.0 31.2 35.5 61.1 31.8 29.4 11.1 13.9 12.5 13.8 13.6 0.875 0.625...
  • Page 4 DISCH LIQUID DIAMETER DIAMETER COND EVAP EVAP RETURN DISCH LIQUID EVAP SUPPLY DUCT WIDTH HEIGHT DEPTH UNIT SWAGE SWAGE SECTION SECTION DUCT CONN CONN (Blower Opening) 50XCR (ID) (ID) 68.0 64.0 31.2 35.5 61.1 31.8 29.4 11.1 13.9 12.5 13.8 2.7 13.6 0.875 0.625 68.0...
  • Page 5 DISCH LIQUID COND EVAP EVAP RETURN DISCH LIQUID EVAP SUPPLY DUCT WIDTH HEIGHT DEPTH UNIT SWAGE SWAGE SECTION SECTION DUCT CONN CONN (Blower Opening) 50XCR (ID) (ID) 88.0 66.7 31.2 31.2 35.5 83.7 33.8 32.3 10.8 13.9 12.5 13.8 13.5 11.7 1.125 0.625...
  • Page 6 DISCH DIA LIQUID DIA COND EVAP EVAP RETURN DISCH LIQUID EVAP SUPPLY DUCT (Blower WIDTH HEIGHT DEPTH SWAGE (ID) SWAGE (ID) UNIT SECTION SECTION DUCT CONN CONN Opening) 50XCR 88.0 66.7 31.2 31.2 35.5 83.7 33.8 32.3 10.8 13.9 12.5 13.8 13.5 11.7...
  • Page 7: Step 1 - Complete Pre-Installation Checks

    Table 2 — Physical Data UNIT 50XCR UNIT OPERATING WEIGHT (lb) 1001 1079 1231 1629 COMPRESSOR Scroll Compressor Model ZPS60 ZPS67 ZP54/ZP49 ZP61/ZP57 ZP91/ZP67 ZP122/ZP91 Steps of Control Operating Charge R-410A (lb)* 11.9 11.5 31.5 EVAPORATOR FAN Adjustable, Belt Drive, Centrifugal Type Nominal Cfm 1750 2600...
  • Page 8: Step 3 - Install Evaporator (Supply) Ductwork

    Fig. 1-5. Recommended line sizes are given in Table 3. Refer to Carrier System Design Manual, Part 3, for standard refriger- ant piping techniques. Remote condenser units are shipped with a holding charge...
  • Page 9: Step 8 - Complete Electrical Connections

    Unit operation on improper line voltage or excessive phase Fig. 8 — External Trap Condensate Drain imbalance may be considered abuse and any resulting damage may not be covered by Carrier warranty. Step 8 — Complete Electrical Connections All wiring must be in accordance with local or NEC GENERAL —...
  • Page 10 Table 4 — Electrical Data VOLTAGE COMPRESSOR COMPRESSOR UNIT RANGE NO. 1 NO. 2 V-PH-Hz 50XCR 208/230-3-60 18.3 — — 460-3-60 — — 575-3-60 — — 208/230-3-60 23.0 — — 460-3-60 11.0 — — 575-3-60 — — 208/230-3-60 15.6 15.9 460-3-60 575-3-60 208/230-3-60...
  • Page 11: Step 9 - Install Plenums (If Required)

    50XC (12 SIZE UNIT AND LARGER) UNIT GROUND WIRE NUT SHIELD (CUT AND TAPE BACK) RS+5 REMOTE ROOM a50-8510 SENSOR (P/N ZONECCORRS01) RS GND 33CS250-01 NOTE: Remote sensor is field-installed option. Fig. 9 — Typical Thermostat Wiring Connections Step 9 — Install Plenums (if Required) — installation of 50XCR plenums is applicable to all vertical dis- charge 50XCR units.
  • Page 12: Start-Up

    3. Set selector switch on thermostat to the ON position. Ad- START-UP just evaporator fan speed. If an airflow is not specified, use the nominal airflow from Table 2 and adjust the fan CAUTION speed to compensate for actual job conditions. Use Tables 6-11 to determine proper fan speed.
  • Page 13 Table 7 — Evaporator Fan Performance — 50XCR08 Units ESP (in. wg) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 2200 0.27 0.39...
  • Page 14 Table 8 — Evaporator Fan Performance — 50XCR12 Units ESP (in. wg) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 3000 0.26 0.33...
  • Page 15 Table 9 — Evaporator Fan Performance — 50XCR14 Units ESP (in. wg) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 3500 0.30 0.46...
  • Page 16 Table 10 — Evaporator Fan Performance — 50XCR16 Units ESP (in. wg) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 4500 0.53 0.69...
  • Page 17 Table 11 — Evaporator Fan Performance — 50XCR24 Units ESP (in. wg) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 6,000 1.10 1.37...
  • Page 18: Compressor Rotation

    Units installed in corrosive environments should be cleaned To determine whether or not Compressor Rotation — as part of a planned maintenance schedule. In this type of appli- compressor is rotating in the proper direction: cation, all accumulations of dirt should be cleaned off the coil. 1.
  • Page 19: Concentric Alignment

    Shaft and wheels must be Concentric Alignment — concentrically centered with the venturi or air inlet of the fan housing (see Fig. 12). a50-2178tf Shaft bearings are supported by bearing supports (Fig. 13). If shaft and wheels are concentrically misaligned from ship- ping shock, it is possible to rebend the bearing support arms to the original positions.
  • Page 20: Maintenance

    MAINTENANCE WARNING The unit should be thoroughly cleaned inside Cleaning — and out. Frequency of cleaning will depend on unit location To prevent personal injury, wear safety glasses and gloves and area conditions. Drains must be kept free of dirt and trash. when handling refrigerant.
  • Page 21: Troubleshooting

    TROUBLESHOOTING Refer to Table 14 to determine the possible cause of the problem and the associated procedure necessary to correct it. See Fig. 15-17 for typical wiring schematic. Table 14 — Troubleshooting Procedure PROBLEM POSSIBLE CAUSE CORRECTION PROCEDURE Unit will not Start Loss of unit power Check power source.
  • Page 22 Table 14 — Troubleshooting Procedure (cont) PROBLEM POSSIBLE CAUSE CORRECTION PROCEDURE Discharge Pressure too Outdoor temperature too low Install low-ambient control. Condenser airflow too high Check and adjust. Low charge Check for and repair leaks and add refrigerant as necessary. Compressor fault Check suction and discharge pressure.
  • Page 23 DISC1 IFC/IFR 208/230V 100/BLK 103/BLK 106/BLK 101/BLK 104/YEL 107/YEL 109/GRN 60 Hz 102/BLK 105/BLU 108/BLU CLO1-Loop COMP1 118/BLK 121/BLK 119/YEL 122/YEL 124/GRN 120/BLU 123/BLU 125/BLK 126/BLK CLO2-Loop COMP2 127/BLK 130/BLK 128/YEL 131/YEL 133/GRN 129/BLU 132/BLU 134/BLK 135/BLK TRAN1 150/BLK 500/BRN 240V 208V 151/YEL...
  • Page 24 Continued on Line Continued on Line Voltage Diagram Voltage Diagram Page 22 FIELD T’STAT LPS1 HPS1 FRZ1 CLO1 LOGIC Start/Stop Relay in LPS2 HPS2 FRZ2 Remote Condenser CLO2 LOGIC a50-8517 NOTE: See legend and notes on page 23. Fig. 15 — Typical Wiring Schematic (50XCR12-24, 208/230-3-60 Units Shown) (cont)
  • Page 25 DISC1* IF VFD 460V 100/BLK 103/BLK 106/BLK 101/BLK 104/YEL 107/YEL 60 Hz 102/BLK 105/BLU 108/BLU 140/GRN 109/GRN 140/GRN USE COPPER SUPPLY WIRES. CLO1-Loop Phase rotation 118/BLK 121/BLK sequence is 119/YEL 122/YEL COMP1 BAC (L2-L1-L3). 120/BLU 123/BLU 125/BLK 126/BLK CLO2-Loop 127/BLK 130/BLK 128/YEL 131/YEL...
  • Page 26 711/VIO 710/BRN 710/BRN 713/BLU 714/YEL Continued on Line Continued on Line Voltage Diagram Voltage Diagram Page 25 504/RED 601/RED REMOVE 509/BRN JUMPER BLK/600 604/BRN WHEN 510/BLK CONNECTING AIR-SIDE 602/BLU ECONOMIZER 608/PNK OCCUPANCY 507/ORN 542/BLU CONTROL 518/BLU 550/BLK LPS1 HPS1 FRZ1 522/BLU 603/YEL 544/YEL...
  • Page 27 Continued on Line Continued on Line Voltage Diagram Voltage Diagram 504/RED 601/RED REMOVE 509/BRN JUMPER BLK/600 604/BRN WHEN 510/BLK CONNECTING AIR-SIDE 602/BLU ECONOMIZER 608/PNK OCCUPANCY 507/ORN CONTROL 550/BLK LPS1 HPS1 FRZ1 522/BLU 603/YEL 544/YEL CLO1 LOGIC 529/BRN 529/BRN ECON 543/BRN WHEN FIELD TIMER1 INSTALLED, THE...
  • Page 30 © Carrier Corporation 2018 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500193-01 Printed in U.S.A. Form 50XCR-6SI Pg 30 1-18 Replaces: 50XCR-5SI...
  • Page 31: Start-Up Checklist

    START-UP CHECKLIST (Fill out this form on Start-Up and file in job folder) NOTE: To avoid injury to personnel and damage to equipment or property when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preced- ing sections of this Installation, Start-Up and Service document.
  • Page 32 SUPPLY FAN AMPS: NOTES: _______________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ © Carrier Corporation 2018 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500193-01 Printed in U.S.A. Form 50XCR-6SI...

Table of Contents