Carrier Omnizone 50XJ050 Controls, Start-Up, Operation And Troubleshooting
Carrier Omnizone 50XJ050 Controls, Start-Up, Operation And Troubleshooting

Carrier Omnizone 50XJ050 Controls, Start-Up, Operation And Troubleshooting

Water-cooled indoor self-contained systems with multi-protocol controller 6126

Advertisement

Quick Links

Controls, Start-Up, Operation and
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . .1,2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
MAJOR SYSTEM COMPONENTS . . . . . . . . . . . . . . . 2-6
Controller Processor 6126 (PCB1). . . . . . . . . . . . . . . . 2
I/O Flex Module 8160 (PCB2) . . . . . . . . . . . . . . . . . . . . . 2
Local Interface Display . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Control Module Communication. . . . . . . . . . . . . . . . . . 2
PCB Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Accessory Sensors/Devices . . . . . . . . . . . . . . . . . . . 2
Wiring Control Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . 5
CONTROL AND DISPLAY. . . . . . . . . . . . . . . . . . . . . . 7-17
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
BACview Interface Device . . . . . . . . . . . . . . . . . . . . . . . . 9
Log On to BACview Display . . . . . . . . . . . . . . . . . . . . . . 9
Log Out of BACview Display . . . . . . . . . . . . . . . . . . . . . 9
Change Default User Password . . . . . . . . . . . . . . . . . . 9
Automatic Self-Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Set the Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Configure Schedules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Adjust Set Points. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Configure Basic Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Display/Set Runtime Alarms. . . . . . . . . . . . . . . . . . . . . 13
Display Alarms and Alarm History . . . . . . . . . . . . . . 13
Set Controller Address . . . . . . . . . . . . . . . . . . . . . . . . . . 14
and Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
VFD Control and Display . . . . . . . . . . . . . . . . . . . . . . . . 15
VFD Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17,18
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Water Fill and Air Purge . . . . . . . . . . . . . . . . . . . . . . . . . 17
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-20
Occupancy Determination. . . . . . . . . . . . . . . . . . . . . . . 18
Fan Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Sequence of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . 18
Diagnostic Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . 20-27
Alarms and Alarm Lamps . . . . . . . . . . . . . . . . . . . . . 20
50XJ Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . 22
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . CL-1, CL-2

SAFETY CONSIDERATIONS

Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components, and
equipment location. Only trained, qualified installers and
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500117-01
Troubleshooting
Page
Printed in U.S.A.
Form 50XJ-2T
Water-Cooled Indoor Self-Contained Systems
with Multi-Protocol Controller 6126
service mechanics should install, start up, and service this
equipment.
When working on this equipment, observe precautions in
the literature, on tags, stickers, and labels attached to the equip-
ment, and any other safety precautions that apply. Follow all
safety codes. Wear safety glasses and work gloves. Use care in
handling, rigging, and setting this equipment, and in handling
all electrical components.
Electrical shock can cause personal injury and death.
Shut off all power to this equipment during installation
and service. There may be more than one disconnect
switch. Tag all disconnect locations to alert others not to
restore power until work is completed.
This unit uses a microprocessor-based electronic control
system. Do not use jumpers or other tools to short out
components, or to bypass or otherwise depart from rec-
ommended procedures. Any short-to-ground of the con-
trol board or accompanying wiring may destroy the
electronic modules or electrical components.
DO NOT USE TORCH to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and gog-
gles and proceed as follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from sys-
tem using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen
and the work area should be well ventilated. Refrig-
erant in contact with an open flame produces toxic
gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit. Use a pan to catch
any oil that may come out of the lines and as a gage
for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when nec-
essary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal
injury or death.
Pg 1
Omnizone™
50XJ050-104
WARNING
CAUTION
WARNING
8-14
Replaces: 50XJ-1T

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Omnizone 50XJ050 and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier Omnizone 50XJ050

  • Page 1: Table Of Contents

    Omnizone™ 50XJ050-104 Water-Cooled Indoor Self-Contained Systems with Multi-Protocol Controller 6126 Controls, Start-Up, Operation and Troubleshooting service mechanics should install, start up, and service this CONTENTS equipment. Page When working on this equipment, observe precautions in SAFETY CONSIDERATIONS .....1,2 the literature, on tags, stickers, and labels attached to the equip- GENERAL .
  • Page 2: General

    VAV (variable air volume) applications. Units are REMOTE OCCUPANCY CONTROL (PCB1) — This con- equipped with Carrier multi-protocol controls. Refer to the unit trol is a field located switch, controller or timer input which, Installation Instructions for unit layout.
  • Page 3 Table 1 — Control Inputs and Outputs DESCRIPTION ABBREV. TYPE I/O NO. JUMPER SETTINGS INPUTS MAIN CONTROLLER (PCB1) Aux. Pwr Out: 24V Refrigerant Pressure (Cir. no. 1) PRES 0-5V; Internally Powered UI-01 IN01: 0-10V Duct Static Pressure 4-20mA; Internally Powered UI-02 IN02: 0-20mA Duct High Static Limit Switch...
  • Page 4 SPACE TEMPERATURE SENSOR (PCB2) — A field-sup- flow control valve is same as for variable waterflow systems. plied Carrier space temperature sensor is required to maintain Control of the reverse flow control valve position will inversely space temperature in sensor mode.
  • Page 5: Wiring Control Devices

    economizer coil or heating coil, is a factory-installed averag- • To determine supply-air temperature reset, occupied ing air temperature sensor positioned in the unit inlet airstream. heating, unoccupied heating and cooling (refer to This may be either a thermistor sensor (automatic reset) or a Sequence of Operation in Operation section).
  • Page 6 SMOKE DETECTOR/FIRE ALARM SHUTDOWN (FSD) ALARM (ALARM) OUTPUT (PCB1) — A Form C dry (PCB1) — To allow a smoke detector to shut the unit down, contact is provided to signal when the controller has an active remove the jumper from terminal block J4, terminals 19 and 20 alarm.
  • Page 7: Control And Display

    turn components on or off. The universal inputs are used to CONTROL AND DISPLAY monitor input from various sensors. These universal inputs can The microprocessor-based controller pro- Controller — be set for one of three different sensor input types: vides complete system control of unit operation. See Fig. 3 for 1.
  • Page 8 ® Universal BACnet Input 0-10V IO Flex 6126 Class 2 Therm 24VAC, 50-60 Hz 20VA, 0.83A 26VDC, 0.17A, 4W 0-20mA Mode Use Copper Select Even Odd Conductors Only UI-12 24VAC Power Switch UI-11 UI-10 UI-09 Power UI-08 Battery UI-07 Batt UI-06 CR2032 UI-05...
  • Page 9: Bacview Interface Device

    switches back the screen where the [LOGIN] softkey was The BACview keypad/ BACview Interface Device — pressed. display features a numeric keypad, direction keys, four func- tion keys, and a backlit LCD (liquid crystal diode) display. See The system will Log Out of BACview Display —...
  • Page 10 HIGHLIGHTED CONTRAST FIELD IN SCREW BRACKETS BACview SELECTED CHARACTER IS MENU: < ALARM > UNOCCUPIED UNDERLINED OAT:000.0 °F LAT:000.0 °F SHUTDOWN:[Off] 100% OA PROGRAM” ][ CANCEL ][ DECR INCR SOFTKEY LABEL SOFTKEY MUTE • ENTER HOTKEYS ARROW KEYS Rnet a62-573 Local Access Fig.
  • Page 11: Set The Clock

    This test will operate the number of compressors indicated The user must be logged on as User or Admin to configure on the "# of Comps" section of the BASE CONFIG screen. the schedules using following procedure. 1. As the alarm relay closes, Compressor 1 starts and NORMAL (LOCAL) SCHEDULES operates for 5 seconds.
  • Page 12: Adjust Set Points

    If viewed as a single large screen, the layout is as follows: ride. The NEXT item at the bottom of screen moves you to the next override schedule set point. --------------------- Holiday Schedule #1 --------------------- Setting the month or day or start time and end time to 0 dis- ables the override schedule.
  • Page 13: Configure Basic Unit

    The user must be logged on Configure Basic Unit — Table 5 — Configuration Menu as Admin to adjust these control configurations. POINT NAME DEFAULT OPTIONS 1. From the HOME menu, select the press the [CONFIG] softkey to enter the CONFIGURATION menu. Always Occupied Local Schedule 2.
  • Page 14: Set Controller Address

    Perform the following procedure to assign an address: Table 6 — Unit Status Menu 1. Turn off the UPC Open XP power switch. STATUS POINT INDICATORS 2. Using the rotary switches, set the controller address. Set the Tens (10’s) switch to the tens digit of the address, and Fan Only set the Ones (1’s) switch to the ones digit.
  • Page 15: Vfd Control And Display

    11. Use the UP/DOWN keys to select "20 Limits" and press display screen. The function of SOFT KEY 2 matches the [SEL]. word in the lower right-hand box on the display screen. If the box is empty, then the SOFT KEY does not have a func- 12.
  • Page 16 A stationary arrow indicates that the drive is stopped. For 4. Press EXIT (SOFT KEY1) to exit the Changed Parame- Carrier air handler units, the rotation is always forward. ters mode. Using parameter group 34, the middle of the LCD dis- Drive Parameter Backup Mode —...
  • Page 17: Start-Up

    5. The text “Restoring Parameters” will be displayed with a 6. Press EXIT (SOFT KEY 1) twice to return to the main progress indicator. To stop the process, select ABORT menu. (SOFT KEY 1). 6. When the download is complete, the text “Parameter START-UP download successful”...
  • Page 18: Operation

    turn on. Thirty seconds later the output to the VFD will in- crease. The VFD output level is determined by a PID calcula- tion, based on the duct static pressure (DSP) input and the sup- ply static pressure set point. Once the supply fan is running and the static pressure increases above the supply fan status set point the supply fan status point (SFS) will indicate ON.
  • Page 19: Diagnostic Features

    (TRMCT) closes a set of relay contacts valve will modulate in reverse of the economizer valve using to indicate to non-Carrier air terminals that the fan is on and op- the formula MVLV = 100 - ECONO.
  • Page 20: Troubleshooting

    FIRE INPUT (FSD) — This is a normally closed input con- compressor, and is set to open at pressures below 27 psig. The nected to the controller. When this input is opened, all control LPS is wired in the 24-vac control power line of the outputs are immediately turned off, including the fan.
  • Page 21 will be lit. An alarm with an ID of "dhs_alarm" will be compressor, the compressor will be locked out pending a pow- generated. er reset or the end of the cooling cycle (no cooling demand). FIRE/SHUTDOWN INPUT (FSD) — This is a normally When a compressor is locked out or the controller detects closed input, which when opened, all control outputs are im- compressor operation with no call for that compressor, the...
  • Page 22: 50Xj Wiring Diagrams

    be generated. This error disables tenant (unoccupied) override an alarm with an ID of "oat_alarm" will be generated if the by the SPT sensor and prevents use of this sensor value in the temperature input exceeds 120 F or falls below 35 F. The alarm cooling/heating mode determination and the supply air reset output will close and the red alarm lamp will light;...
  • Page 23 LEGEND AND NOTES FOR FIG. 11 AND 12 LEGEND NOTES: 1. Partial wiring shown on both power and control diagrams. BPS_S — Fan Start/Stop Relay (VFD Bypass Mode) 2. All class 2 transformers are wired into separate circuits. Do not —...
  • Page 24 a50-8461 a50-8752...
  • Page 25 a50-8462...
  • Page 26 a50-8463 Fig. 12 — Typical Low Voltage Control Wiring Diagram...
  • Page 27 a50-8464 LON Port 2b*...
  • Page 30  Carrier Corporation 2014 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500117-01 Printed in U.S.A. Form 50XJ-2T Pg 30 8-14 Replaces: 50XJ-1T...
  • Page 31: Start-Up Checklist

    START-UP CHECKLIST (Fill out this form on Start-Up and file in job folder) I. PRELIMINARY INFORMATION: MODEL NO. ____________________ SERIAL NO. ____________________ 50XJ UNIT: FIELD-INSTALLED ACCESSORIES: _____________________________________________________________________ START-UP DATE: ______________________________________ II. PRE-START-UP: VERIFY ALL SHIPPING MATERIALS HAVE BEEN REMOVED FROM THE UNIT IS THERE ANY SHIPPING DAMAGE? ________________ IF SO, WHERE ________________ _________________________________________________________ WILL THIS DAMAGE PREVENT UNIT START-UP?(Y/N) _______...
  • Page 32 SUPPLY FAN AMPS: NOTES: _______________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ © Carrier Corporation 2014 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500117-01 Printed in U.S.A. Form 50XJ-2T...

This manual is also suitable for:

Omnizone 50xj104

Table of Contents