10.3

Connection of Sensors, Outputs and Power Supply

Cables connected to the VC-18xx must be suitable for an ambient temperature
of -10 ° C to + 80 ° C
External strain relief of the cables is recommended
The shields of the incoming and outgoing cables must be laid on suitable equipotential bonding.
The following order is recommended during installation:
1. Connect the sensors
2. Connect the relay and analog outputs
3. Connect the power supply

10.3.1 VIBROCONTROL 1850 Terminals

CCS accelerometers
The 2-wire accelerometers are connected to the terminals (signal (Input+) and GND (Input-)). Up to
4 accelerometers can be connected to a VC-1850:
Additional sensor connections are:
Sensor 2: 16 (Input 2+) / 15 (Input 2-) sensor 3: 17 (Input 3+) / 18 (Input 3-)
Sensor 4: 20 (Input 4+) / 19 (Input 4-)