Brüel & Kjær Vibro │ Instruction VC-1800 Series
6.4

Setting of the Outputs (Analog Output or Relay)

The VIBROCONTROL 18xx has four configurable outputs on
terminals #9, #10, #11 and #12. Each of these outputs can be enabled or disabled. An enabled
output can have any of these output functions:
A solid-state relay, which is closed and connected to ground (GND)
when not enabled. When enabled the relay breaks.
An analog DC current output of 0-20 mA or 4-20 mA, directly proportional to the measured
parameter between 0 and full scale.
An analog DC voltage output of 0-10 volts or 2-10 volts, directly proportional to the measured
parameter between 0 and full scale.
© Brüel & Kjær Vibro ● C106834.002 / V06 ●
Technical alterations reserved!
Installation and Operation of VIBROCONTROL
UNRESTRICTED DOCUMENT
EN
18xx
Page 23 of 110