Make/Break Relays; Mounting - BRUEL & KJAER VIBROCONTROL 1800 Series Instructions Manual

Four-channel vibration monitors
Hide thumbs Also See for VIBROCONTROL 1800 Series:
Table of Contents

Advertisement

EN
NOTE!
Only connect one measurement module with a relay module at a time.
8.1.3

Make/Break Relays

All relays of a VC-1801 relay module are by default configured to go from the "make" to the "break"
status when the associated alarm in a VIBROCONTROL 18xx is activated.
This has the advantage that the relays will act as being activated in case of a power failure.
8.1.4

Mounting

The relay modules VIBROCONTROL 18xx and VC-1801 must be positioned next to each other
with the two 5-pin DIN-rail bus connectors:
The VC-1801 relay module can be positioned on either side.
WARNING!
No more than one (1) VC-1850/60/70 can be connected with a VC-1801 relay module with the
same DIN-rail bus.
Page 56 of 110
© Brüel & Kjær Vibro ● C106834.002 / V06
Technical alterations reserved!