Monitor" View; Self-Test - BRUEL & KJAER VIBROCONTROL 1800 Series Instructions Manual

Four-channel vibration monitors
Hide thumbs Also See for VIBROCONTROL 1800 Series:
Table of Contents

Advertisement

EN
6.2

"Monitor" View

The "Monitor" page of the Compact Setup software shows the basic functions.
6.3

Self-Test

The VIBROCONTROL 18xx includes a "Self-test" function that can be enabled externally. This can
be done by connecting a ground (GND) signal to terminal #8 on the enclosure or by using the
Compact Commander software to enable the self-test.
Only individual functions can be addressed during a self-test. But there are NO consequences, i.e.
no alarms will be triggered if a certain vibration level set during self-test exceeds an alarm trigger
level.
If an alarm must be triggered during self-test, the alarm in question must be marked. The behavior
of outputs during a self-test must also be specified separately.
Thus, the user will have to specify/set the following in connection with a self-test:
The unit for each vibration parameter, for example mm/s.
The status of alarms during a self-test.
All four outputs, either as status of a relay or a certain measured value for:
-
DC current (mA) or
-
DC voltage (V).
The process input must be specified in detail (measuring range and alarms).
The "Status" LEDs flash yellow for the duration of the self-test.
Page 22 of 110
© Brüel & Kjær Vibro ● C106834.002 / V06
Technical alterations reserved!