Hitachi RPIL-3.0UFE1NH Service Manual page 29

Hide thumbs Also See for RPIL-3.0UFE1NH:
Table of Contents

Advertisement

2.TROUBLESHOOTING
Fault
Fault description
code
1
Inverter DC voltage overload fault 1. Power supply input is too high
2
Inverter DC low voltage fault
3
Inverter AC current overload fault
4
Out-of-step detection
Loss phase detection fault (speed
5
pulsation)
Loss phase detection fault (current
6
imbalance)
7
Inverter IPM fault (edge)
8
Inverter IPM fault (level)
9
PFC_IPM IPM fault (edge)
10
PFC_IPM IPM fault (level)
11
PFC power detection of failure
PFC overload current detection of
12
failure
13
DC voltage detected abnormal
PFC LOW voltage detected
14
failure
AD offset abnormal detected
15
failure
16
Inverter PWM logic set fault
17
Inverter PWM initialization failure
18
PFC_PWM logic set fault
19
PFC_PWM initialization fault
Temperature is abnormal
20
Shunt resistance unbalance
21
adjustment fault
22
Communication failure
Motor parameters setting of failure Initialization is abnormal.
23
EE data is abnormal
25
26
DC voltage mutation error
27
D axis current control error
28
Q axis current control error
Saturation error of D axis current
29
control integral
Saturation error of Q axis current
30
control integral
Table 3 Drive fault code (3.0/3.5HP)
Possible reasons for abnormality
or too low;
2. Driver board fault.
1. Compressor phase lost;
2. Bad driver board components;
3. The compressor insulation fault.
1. System overload or current
overload;
2. Driver board fault;
3. Compressor oil shortage,
serious wear of crankshaft;
4. The compressor insulation fault.
1. The power supply is not stable;
2. Instantaneous power cut;
3. Driver board failure.
1. System overload, current is
too high;
2. Driver board fails;
3. PFC fails.
1. Input voltage is too high or too
low;
2. Driver board fails.
Driver board fails.
1. Communication wire connection
is not proper;
2. Driver board fails;
3. Control board fails.
Driver board EEPROM is abnormal. 1. Change EEPROM;
1. Power input changes suddenly;
2. Driver board fails.
1. System overload, phase current
is too high;
2. Driver board fails.
1. System overload, phase current
is too high;
2. Driver board fails.
1. System overload suddenly;
2. Compressor parameter is
not suitable;
3. Driver board fails.
1. System overload suddenly;
2. Compressor parameter is
not suitable;
3. Driver board fails.
27
How to deal with
1. Check power supply;
2. Change driver board.
1. Check compressor wire
connection;
2. Change driver board;
3. Change compressor.
1. Check the system;
2. Change driver board;
3. Change the compressor;
4. Change the compressor.
1. Check the power supply;
2. No need to deal with;
3. Change the driver board.
1.Check the system;
2.Change the driver board;
3.Change the PFC.
1. Check the power supply;
2. Change the driver board.
Change the driver board.
1. Check the wiring;
2. Change the driver board;
3. Change the control board.
Reset the power supply.
2. Change driver board.
1.Check power supply, to provide
stable power supply;
2.Change the driver board.
1. Check if the system is normal;
2. Check if the stop valve is open;
3. Change the driver board.
1. Check if the system is normal;
2. Check if the stop valve is open;
3. Change the driver board.
1. Check if the system is normal;
2. Check if the stop valve is open;
3. Change the driver board.
1. Check if the system is normal;
2. Check if the stop valve is open;
3. Change the driver board.