2.TROUBLESHOOTING
The following is the fault code table of indoor unit.
Fault
Fault description
code
51
Drainage protection
Mode conflict fault
55
Communication
between Indoor
64
& Outdoor unit
Fault
Indoor unit zero
71
check fault
72
Indoor fan motor fault
Indoor EEPROM
73
Data
1 fault
Table 2 Indoor fault code
Possible reasons for abnormality
1. The water level of the drain
pan exceeds safe level;
2. The cable of the water level
switch is connected loosely;
3.The water level switch fails;
4.The control board fails.
The user sets the conflicting mode
for more than two indoor units.
1. The indoor unit and the outdoor
unit are not connected properly;
2. The communication cable is
connected loosely;
3. The communication cable
between the indoor unit and the
outdoor unit is failure or the cable
between the indoor control board
to terminal fails or the cable
between the outdoor control board
to the terminal fails;
4. The indoor control board fails;
5. The outdoor control board fails.
1. The motor wire is loose;
2. The motor connection is open;
3. The motor fails;
4. Control board fails.
5. Indoor fan is baffled.
1. The cable of the indoor fan
motor is connected loosely;
2. The cable of the indoor fan
motor fails;
3. The indoor fan motor fails;
4. The indoor control board fails.
1.
Indoor EE components fail;
2.
The control circuit of the EE
components fails;
3. The EE components have been
inserted in opposite direction.
How to deal with
1. Check whether there is
something blocking the
drain hose or the drain
hose is too high;
2. Check the water pump and
replace the water pump
if the water pump fails;
3. Reconnect the cable of the
water level switch referring
to the wiring diagram;
4. Replace the water level
switch;
5. Replace the control board.
Reset the operation mode for the
indoor unit, for with one outdoor
unit, the user should avoid setting
the conflicting operation mode
with the indoor units.
1. Reconnect the connection
cable referring to the indoor
and outdoor wiring diagram;
2. Reconnect the
communication cable
referring to the indoor and
outdoor wiring diagram;
3. Replace the communication
cable referring to the indoor
and outdoor wiring diagram;
4. Replace the indoor control
board;
5. Replace the outdoor control
board.
1.Replace the motor wire and
make sure it is connected
well;
2. Replace the motor wire;
3. Change the motor;
4. Change the indoor control
board;
5. Check and eliminate the
fan motor rotation.
1. Reconnect the cable of the
fan motor;
2. Replace the cable of the fan
motor;
3. Replace the fan motor;
4. Replace the indoor control
board;
5. Check the indoor fan and
ensure the indoor fan can
run normally.
1.
Replace the EE components;
2.
Replace the indoor control
board;
3. Reassemble the EE
components of the indoor
control board.