5 Installation
Fig.36
Room-ventilated version
D
Tab.2
Flue gas outlet dimensions
Output (P)kW
Number of boilers dia. D (mm)
(80/60 °C)
294
2
441
3
588
4
735
5
882
6
1029
7
1176
8
Fig.37
Room-ventilated version
D
D
D
40
MCA
D
H
AD-0000862-01
H = 0 - 2 m
150
185
225
250
280
305
325
D
D
H
D
AD-0000863-01
Room-ventilated, high pressure
Sizes of the flue gas outlet/air supply connections: room-ventilated, high
pressure
Connection sizes for MCA 160: ∅ 150/150 mm
Instructions for using the table:
look for the desired output P (in kW at 80/60° C) in the left column.
Then take the available height (H) from the right columns.
If necessary, round up the diameter found to the available size sold.
Important
The boiler's parameter settings will need to be changed. Contact
us for more information.
H = 2 - 5 m
H = 5 - 9 m
150
160
190
195
225
235
255
260
285
290
305
310
330
335
Room-sealed version, high pressure
Sizes of the flue gas outlet/air supply connections: room-sealed version,
high pressure
Connection sizes for MCA 160: dia. 150/150 mm
Instructions for using the table:
look for the desired output P (in kW at 80/60° C) in the left column.
Then take the available height (H) from the right columns.
If necessary, round up the diameter found to the available size sold.
Important
The boiler's parameter settings will need to be changed. Contact
us for more information.
H = 9 - 13 m
H = 13 - 17 m
165
170
200
205
235
240
265
270
295
295
315
320
335
340
7680446 - v.01 - 14082017