COMPRESSORS
The compressor used in this product is specifically designed to operate
with R-410A refrigerant and cannot be interchanged.
CAUTION
!
This system uses R-410A Refrigerant which operates at higher pres-
sures than R-22. No other refrigerant may be used in this system.
The compressor uses polyolester (POE oil), Mobile 3MA POE. This oil
is extremely hygroscopic, meaning it absorbs water readily. POE oil can
absorb 15 times as much water as other oils designed for HCFC and
CFC refrigerants. If refrigerant circuit is opened, take all necessary pre-
cautions to avoid exposure of the oil to the atmosphere.
CAUTION
!
Do not leave the system open to the atmosphere. Unit damage could
occur due to moisture being absorbed by the POE oil in the system.
This type of oil is highly susceptible to moisture absorption
POE (polyolester) compressor lubricants are known to cause long-term
damage to some synthetic roofing materials.
CAUTION
!
Exposure, even if immediately cleaned up, may cause embrittlement
(leading to cracking) to occur in one year or more. When performing
any service that may risk exposure of compressor oil to the roof, take
precautions to protect roofing.
SECTION V: AIRFLOW PERFORMANCE
Table 11: Airflow Performance - Side Duct Application
Model
Motor Speed
Low (1)
Medium Low (2)
PHE4B36
Medium (3)
Medium High (4)
High (5)
Low (1)
Medium Low (2)
PHE4B48
Medium (3)
Medium High (4)
High (5)
Low (1)
Medium Low (2)
PHE4B60
Medium (3)
Medium High (4)
High (5)
Notes:
Airflow tested with dry coil conditions, without air filters, at 230 V.
Applications above 0.8 in. W.C. external static pressure are not recommended.
Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
Minimal variations in airflow performance data result from operating at 208 V. Data above may be used in those cases.
Heating applications tested at 0.50 in. W.C. external static pressure, and cooling applications tested at 0.30 in. W.C.external static pressure per standards.
12
0.1
0.2
0.3
SCFM
SCFM
SCFM
1108
1050
984
1283
1225
1168
1362
1308
1252
1403
1347
1290
1623
1569
1519
1620
1564
1517
1694
1630
1580
1798
1722
1669
1835
1758
1703
2146
2085
2025
1730
1682
1628
1858
1807
1749
2054
1998
1934
2195
2144
2098
2445
2388
2306
Procedures that risk oil leakage include, but are not limited to, compres-
sor replacement, repairing refrigerant leaks, and replacing refrigerant
components such as filter drier, pressure switch, metering device, or
coil.
CAUTION
!
Do not loosen compressor mounting bolts.
Units are shipped with compressor mountings that are factory-adjusted
and ready for operation.
PHASING
Three-phase, scroll compressors operate in only one direction. If the
scroll is drawing low amperage, has similar suction and discharge pres-
sures, or is producing a high noise level, the scroll compressor motor
may be experiencing out of phase rotation and must be corrected.
CAUTION
!
Scroll compressors require proper rotation to operate
properly. Failure to check and correct rotation may result
in property damage.
If necessary, change the incoming line connection phasing to obtain the
proper rotation.
External Static Pressure (in. W.C.)
0.4
0.5
0.6
SCFM
SCFM
SCFM
921
857
791
1115
1054
993
1199
1142
1079
1235
1177
1118
1470
1418
1362
1466
1418
1360
1530
1482
1430
1620
1572
1527
1653
1604
1558
1960
1872
1862
1592
1552
1517
1710
1667
1629
1890
1843
1801
2049
2003
1955
2293
2235
2178
0.7
0.8
SCFM
SCFM
SCFM
726
660
924
860
1015
979
1058
995
1306
1246
1125
1308
1206
1002
1380
1292
1116
1480
1413
1280
1511
1442
1304
1798
1735
1609
1479
1439
1359
1589
1546
1460
1757
1710
1616
1883
1868
1838
2129
2077
1973