INSTALLATION MANUAL
SINGLE PACKAGE
HEAT PUMP/ELECTRIC HEAT
MODELS: PHE4 SERIES
3 TO 5 TONS - 208/230 V - 3 PHASE
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
MODEL NUMBER NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
AIRFLOW PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Unit 4 Point Load Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Bottom Duct Dimensions (in.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Rear Duct Dimensions (in.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Typical Field Power Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . 7
Unit Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Application Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Single Point Wiring Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Electrical Data - 208-3-60 Multi Source Power . . . . . . . . . . . . . . . . . 9
Electrical Data - 230-3-60 Multi Source Power . . . . . . . . . . . . . . . . 10
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
SECTION I: GENERAL INFORMATION
PHE units are factory assembled heat pumps designed for outdoor
installation on a rooftop or a slab. Field-installed optional electric heater
accessories are available to provide supplemental electric heat com-
bined with electric cooling and heating.
The units are completely assembled on rigid, removable base rails. All
piping, refrigerant charge, and electrical wiring is factory installed and
tested. The units require only electric power condensate drain and duct
connections at the point of installation.
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
Johnson Controls Ducted Systems
LIST OF SECTIONS
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
TYPICAL WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
LIST OF FIGURES
Single Point Wiring Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Demand Defrost Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Measuring External Static Pressure . . . . . . . . . . . . . . . . . . . . . . . . . 16
Connection Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Ladder Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
R-410A Quick Reference Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
LIST OF TABLES
Airflow Performance - Side Duct Application . . . . . . . . . . . . . . . . . . 12
Airflow Performance - Bottom Duct Application . . . . . . . . . . . . . . . . 13
Electric Heat Minimum Supply Air . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Electric Heat Multipliers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Additional Static Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Demand Defrost Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Test Pins . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Thermostat Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or maintenance
can cause injury or property damage. Failure to carefully read and
follow all instructions in this manual can result in furnace mal-
function, death, personal injury and/or property damage. Only a
qualified contractor, installer or service agency should install this
product.
This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.
®
WARNING
!
CAUTION
!
5151094-UIM-H-0220

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls PHE4 Series

  • Page 1: Table Of Contents

    SINGLE PACKAGE ® HEAT PUMP/ELECTRIC HEAT MODELS: PHE4 SERIES 3 TO 5 TONS - 208/230 V - 3 PHASE LIST OF SECTIONS GENERAL INFORMATION ....... . 1 OPERATION .
  • Page 2: Model Number Nomenclature

    Air Temperature at Outdoor Coil (°F) Air Temperature at Indoor Coil (°F) Packaged Equipment Minimum Maximum Minimum Maximum Series DB Cool DB Heat DB Cool DB Heat WB Cool DB Heat WB Cool DB Heat 14 SEER HP Johnson Controls Ducted Systems...
  • Page 3: Component Location

    Units may be moved or lifted with a forklift. Slotted openings in the base air discharge outlet. rails are provided for this purpose. CLEARANCES All units require certain clearances for proper operation and service. See Table 5 for the clearances required for construction, servicing, and proper unit operation. Johnson Controls Ducted Systems...
  • Page 4: Unit 4 Point Load Weight

    Table 3: Weights and Dimensions Model Weight (lb) Center of Gravity 4 Point Load Location (lb) Shipping Operating PHE4B36 PHE4B48 PHE4B60 "D" CENTER OF GRAVITY COMPRESSOR "C" "A" FRONT OF UNIT "B" A0295-001 FIGURE 2: Unit 4 Point Load Weight Johnson Controls Ducted Systems...
  • Page 5: Unit Dimensions

    3. Units can be installed on combustible materials made from wood or class A, B, or C roof covering materials if factory base rails are left in place as shipped. Note: For units with a roof curb, the minimum clearance between combustible roof curb material and the supply air duct can be reduced from 1 in. to 1/2 in. Johnson Controls Ducted Systems...
  • Page 6: Bottom Duct Dimensions (In.)

    Check filters monthly. This is especially important because this unit is Model used for both heating and cooling. 13.6 FIGURE 5: Rear Duct Dimensions (in.) Johnson Controls Ducted Systems...
  • Page 7: Typical Field Control Wiring Diagram For Heat Pump Models

    NEC/CEC. Voltage tolerances that must be main- tained at the compressor terminals during starting and running condi- tions are indicated on the unit Rating Plate and Table 1. Johnson Controls Ducted Systems...
  • Page 8: Electrical Data - 208/230-3-60 Single Source Power

    6HK16502025 S1-2SPWK035 n/a* 6HK06501025 S1-2SPWK032 6HK06501525 S1-2SPWK034 PHE4B60 6HK06501825 S1-2SPWK034 6HK16502025 S1-2SPWK035 n/a* 6HK16502525 S1-2SPWK035 n/a* Note: * The 208/230 V 20 kW and 25 kW heater kits include circuit breakers, so no fuse is needed. Johnson Controls Ducted Systems...
  • Page 9: Electrical Data - 208-3-60 Multi Source Power

    14.4 40.0 28.7 25.0 25.0 6HK16502525 18.0 50.0 28.7 31.3 31.3 1. MCA = Minimum Circuit Ampacity. 2. Maximum Over Current Protection per standard UL 1995. 3. Fuse or HACR circuit breaker size is field installed. Johnson Controls Ducted Systems...
  • Page 10: Electrical Data - 230-3-60 Multi Source Power

    17.6 44.2 28.7 27.6 27.6 6HK16502525 22.0 55.2 28.7 34.5 34.5 1. MCA = Minimum Circuit Ampacity. 2. Maximum Over Current Protection per standard UL 1995. 3. Fuse or HACR circuit breaker size is field installed. Johnson Controls Ducted Systems...
  • Page 11: Physical Data

    All three-phase models include an internal filter rack kit and washable filters. Refer to the instructions supplied with the kit for replacement filter sizes. Filter sizes: A = 20 x 20, B = 20 x 30. Johnson Controls Ducted Systems...
  • Page 12: Airflow Performance

    Minimal variations in airflow performance data result from operating at 208 V. Data above may be used in those cases. Heating applications tested at 0.50 in. W.C. external static pressure, and cooling applications tested at 0.30 in. W.C.external static pressure per standards. Johnson Controls Ducted Systems...
  • Page 13: Airflow Performance - Bottom Duct Application

    Table 14: Electric Heat Multipliers Voltage kW Capacity Multipliers Nominal Applied 0.75 0.92 1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat capacity for heaters applied at lower voltages. Johnson Controls Ducted Systems...
  • Page 14: Operation

    ON position, the indoor blower motor continues to run at GSPD. If the fan switch is in the AUTO For extreme environments as necessary only. position. the indoor motor ramps down after a 60-s delay. Johnson Controls Ducted Systems...
  • Page 15: Demand Defrost Control

    Outdoor ambient sensor failure (Open or Shorted) 9 Flashes Reversing valve de-energized Control Failure 10 Flashes Indoor blower switches to continuous fan speed * Motor program has 60-s blower off delay on all 5 speed taps. Johnson Controls Ducted Systems...
  • Page 16: Measuring External Static Pressure

    3. Treat the negative number as a positive and add the two numbers 8. Make sure all unit panels are in place and secured, and that an air together. This is total system static. filter is installed. FIGURE 10: Measuring External Static Pressure Johnson Controls Ducted Systems...
  • Page 17: Maintenance

    Cleaning should be as often as necessary to keep the coil clean. If water is used to clean the coil, ensure the power to the unit is shut off before cleaning. Johnson Controls Ducted Systems...
  • Page 18: Typical Wiring Diagrams

    8. BLOWER MOTOR SPEED CONNECTIONS SHOWN ARE TYPICAL, BUT MAY VARY BY MODEL AND APPLICATION. MOVE BLACK WIRES FROM THE 230 TO THE 208 VOLT TAP ON THE TRANSFORMER. 4. MOTORS ARE INHERENTLY PROTECTED. 5146414-UWD-A-0715 FIGURE 11: Connection Wiring Diagram Johnson Controls Ducted Systems...
  • Page 19: Ladder Wiring Diagram

    3. FACTORY WIRED FOR 230 VOLT THREE-PHASE SUPPLY POWER. FOR 208 VOLT, MOVE BLACK WIRES FROM THE 230 TO THE 208 VOLT TAP ON THE TRANSFORMER. BUT MAY VARY BY MODEL AND APPLICATION. 4. MOTORS ARE INHERENTLY PROTECTED. FIGURE 12: Ladder Wiring Diagram Johnson Controls Ducted Systems...
  • Page 20: R-410A Quick Reference Guide

    Never open system to atmosphere when under a vacuum. If system must be opened for service, evacuate system then break the vacuum with dry nitrogen and replace all filter driers. FIGURE 13: R-410A Quick Reference Guide Johnson Controls Ducted Systems...
  • Page 21: Start Up Sheet

    Supply air dry bulb temperature Outside air dry bulb temperature Return static (inches of water column) Return air dry bulb temperature Return air wet bulb temperature Total external static pressure Temperature drop Supply air wet bulb temperature Johnson Controls Ducted Systems...
  • Page 22 Explain the importance of regular filter replacement and equipment maintenance Comments and Additional Job Details Subject to change without notice. Published in U.S.A. 5151094-UIM-H-0220 Copyright © 2020 by Johnson Controls. All rights reserved. Supersedes: 5151094-UIM-G-0417 York International Corp. 5005 York Drive...