Final Checks (With Burner Operating) - Riello PRESS 450 T/N Installation, Use And Maintenance Instructions

Heavy oil burner
Hide thumbs Also See for PRESS 450 T/N:
Table of Contents

Advertisement

8.2

Final checks (with burner operating)

 Block out the UV sensor and switch on the control
devices:
 Block out the UV sensor when the burner is operating:
 Switch off the TL control device and then the TS device
when the burner is operating:
Make sure that the mechanical locking systems
on the various adjustment devices are fully tight-
ened.
ATTENTION
20184179
Burners start-up cycle diagnostics
26
GB
the burner should start and then go into lockout after about
10 seconds from the opening of the 1st stage working
valve.
the flame should switch off within 1 sec., as also the repeti-
tion of the starting cycle and then the stopping of the burner.
the burner must stop.
Tab. M