Temperature adjustment

The displayed room temperature can deviate from the
actual room temperature if your Vitotrol 100 is installed
in an unfavourable position, e.g. on an external wall or
near a chimney. You can correct this temperature devi-
ation with an adjustment.
Example:
The room temperature displayed by the Vitotrol 100 is
2
C higher than the actual room temperature. The cor-
º
rection is then
2
C.
º
01. Open the flap.
02. Press
twice.
03. With / select "Settings".

Control characteristics

The hysteresis controller is factory-set. The hysteresis
value influences the start and stop times for "Heating"
or "Not heating".
Example:
Set room temperature: 21
Hysteresis: 0.6
C (factory setting).
°
Setting range: 0.2 to 1.0
Heating stops as soon as the actual room temperature
exceeds 21.3
C. Heating starts as soon as the actual
°
room temperature falls below 20.7
You can change the control characteristics by chang-
ing the hysteresis value. Select a lower value if your
system responds too slowly.
1. Open the flap.
2. Press
twice.
3. With / select "Settings".
4. Confirm with OK.
5. With / select "Service".
6. Confirm with OK.
7. With / set the required hysteresis value.
8. Confirm twice with OK.
9. Exit the menu with
C
°
C.
°
C.
°
.
04. Confirm with OK.
05. With / select "Service".
06. Confirm with OK.
07. With OK select the required value to be set for
"Ctrller offset".
08. With / set the required value.
09. Confirm with OK.
10. Exit the menu with
Further adjustments
.