[ENG] 9. [DKST 57]Factory reset device

The reset procedure returns all configurable device parameters to default values (IP and MAC addresses, access
filters, username, password, etc.) to their default values. 
To reset the parameters to their default values, follow these steps in sequence: 
Turn off the power of the device (disconnect the external battery module); 
Press the Reset button; 
Turn on the power of the device, continuing to hold the Reset button pressed for 15-20 seconds; 
Release the button. All device parameters are reset to default values. 
After resetting the parameters to the default values, it is necessary to perform the initial configuration of the
device. 
A short press on the «reset» button reboots the device.
By default, the device has the following parameters:
Web-interface login: visor
Password: ping
IP address: 192.168.0.100
Mask: 255.255.255.0
Gateway: не установлен
SNMP community: SWITCH
MAC-address: 00 a2 xx xx xx xx
Here xx xx xx xx corresponds to the serial number of the device. Thus, all devices after production have
unique MAC addresses. 