[ENG] 8. [DKST 57]Use of IN, OUT and RELAYS lines.

Attention!
On device output lines 12 V, up to 250 mA. If used incorrectly, the connected equipment may be
damaged.
The device has sixteen INPUT lines corresponding to the IN 1 - IN 16 contacts of the terminal block, four OUTPUT
lines corresponding to the OUT 1 - OUT 4 contacts and 4 RELAYS outputs with a changeover contact of the NO-COM-
NC type. Configuring INPUT, OUTPUT and RELAYS lines for operation is performed through the control web
interface of the device. All sixteen INPUT lines, 4 OUTPUT and 4 RELAYS can be configured independently of each
other.
OUTPUT lines and RELAYS can be controlled using SNMP commands, HTTP API commands, via the web interface or
via SMS commands using a NetPing SMS device.
Examples of using:
remote reboot of servers - imitation of pressing the Reset button;
remote control of siren, lighting, fan;
control of an electric lock, electric turns at a remote object;
control of "smart home" elements: watering plants, opening and closing blinds, water pump, heating boiler,
electric heaters and more;
remote control of the power plant (diesel generator, gas generator);
integration into security systems and emulation of sensor triggering.
Important! Correct electrical coordination of INPUT, OUTPUT lines and RELAYS is required when
connecting external actuators
Important! OUTPUT lines are not galvanically isolated from the device! When using relays that switch 220
V circuits, remember about electrical safety. All work must be carried out by specialists with the
appropriate qualifications and permission to work with this voltage.
It is possible to use intermediate relays with a supply voltage from an external 12V source. A controlled NetPing AC /
DIN socket can be used to connect to OUTPUT lines.
For more information, please contact technical support on e-mail: support@netpingdevice.com

Electrical parameters INPUT, OUTPUT lines and RELAYS

OUTPUT - line:
logic. 1: pull-up +12 V  200 mA;
logic. 0 : 0 V, до 200 мА.
The total load on the outputs in the OUT-UP mode should not exceed 250mA. Each pin is protected against
short circuits by a self-resetting 250mA fuse.
[ENG] NetPing Input+Relay R404, User guide -[ENG] 8. [DKST 57]Use of IN, OUT and RELAYS lines.