Service Manual
Overcurrent
20
protection of
P5
phase current
21 Defrosting
Overload
22
protection of
H3
compressor
IPM
23
H5
protection
Installation and Maintenance
Flash
15 times
every 3s
ON 10s
and OFF
0.5s
Flash
3 times
every 3s
Flash
5 times
every 3s
During cooling
and drying
operation,
compressor and
outdoor fan stop
while indoor
fan operates.
During heating
operation, all
loads stop.
During cooling
and drying
operation,
compressor and
outdoor fan stop
while indoor
fan operates.
During heating
operation, all
loads stop.
During cooling
and drying
operation,
compressor and
outdoor fan stop
while indoor
fan operates.
During heating
operation, all
loads stop.
See 9.3
(diagnosis of
IPM protection,
desynchronizing
Refer to
malfunction,
maintenance
overcurrent
flowchart
protection of
phase current of
compressor)
Normal function
1:Wiring
terminal OVC-
COMP is loose
1. After de-
(Under normal
energization,
circumstances,
insert OVC-
the resistance
COMP terminal
between both
tightly;
ends of this
terminal should
be less than 1Ω.)
2: See 9.3
(diagnosis of
2. Refer to
overload and
maintenance
discharge
flowchart
protection)
See 9.3
(diagnosis of
IPM protection,
desynchronizing
Refer to
malfunction,
maintenance
overcurrent
flowchart
protection of
phase current of
compressor)