Lennox LNINVE052 Service Manual page 58

Refrigerant r410a
Table of Contents

Advertisement

Service Manual
Malfunction
of outdoor
12
ambient
temperature
sensor
Malfunction
of outdoor
13
condenser
temperature
sensor
Malfunction
of outdoor
14
discharge
temperature
sensor
Limit/
decrease
15
frequency
due to
overload
Decrease
frequency
16
due to
overcurrent
Installation and Maintenance
Flash
F3
3 times
every 3s
Flash
F4
4 times
every 3s
Flash
F5
5 times
every 3s
Flash
F6
6 times
every 3s
Flash
F8
8 times
every 3s
During cooling
and drying
operation,
compressor and
outdoor fan stop
while indoor
fan operates.
During heating
operation, all
loads stop.
During cooling
and drying
operation,
compressor and
outdoor fan stop
while indoor
fan operates.
During heating
operation, all
loads stop.
During cooling
and drying
operation,
compressor and
outdoor fan stop
while indoor
fan operates.
During heating
operation, all
loads stop.
All loads
operates
normally, while
operation
frequency of
compressor
decreases.
All loads
operates
normally, while
operation
frequency of
compressor
decreases.
1. After de-
1.T-SENSOR
energization,
terminal hasn't
reinsert
been inserted
T-SENSOR
tightly;
terminal tightly;
2. Hardware
2. Replace
malfunction of
outdoor unit's
outdoor unit's
main board
main board;
AP1;
See
9.3(diagnosis
Refer to
of overheating
maintenance
prevention
flowchart
and overload
protection)
1. Check
Input power
whether power
voltage is too
supply network
low;
is abnormal;
Pressure of
2. Reduce
system is too
load;
high; overload
55

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents