Maintenance; Troubleshooting; Table 7-1: Troubleshooting - NBN Fluke CS400 Hardware Manual

Kiln shell temperature monitoring
Table of Contents

Advertisement

CS400 System
Hardware Manual, Rev. 1.0, Sep 2021

7 Maintenance

You can find a troubleshooting guide for common system problems in the Linescanner manual.
System specific problems you can find listed below.

7.1 Troubleshooting

Checkpoint
Kiln Trigger
Ethernet Communication
via Fiber Optic
TSM
To get quick help send a detailed error report to the TechSupport Team of the manufacturer
46

Table 7-1: Troubleshooting

Possible Cause / Solution
The system has lost synchronization due to missing signals from the position indicator:
• Check alignment and distance between trigger bar and position indicator.
• Increase the metal mass of the trigger bar for a reliable signal generation.
• Check the wiring.
Note: The trigger signal can be verified by a blinking LED on the junction box located close to the position
indicator!
If there is no communication after installation and powering of all components required - please check the
'cross-over' of the two fibers between the glass fiber converter in the field and the control room (TX is in all
cases to be connected to RX of the other converter)!
Use only position indicators supplied from the manufacturer!
including the current configuration files!
Note