Figure 4-2: Protective Housing With Protective Channel - NBN Fluke CS400 Hardware Manual

Kiln shell temperature monitoring
Table of Contents

Advertisement

CS400 System
Hardware Manual, Rev. 1.0, Sep 2021
Installing the linescanner
Open the back door. Insert the linescanner (with the mounted carrier) into the rail/carrier system. Lock in the
linescanner in place with the latches and screw.
Electrical Installation
For best performance, the electrical installation of the CS400 System should correspond to one of the
recommended installation configurations illustrated in section 8.2
Connecting the cables
The cables W1, W3, and W18 (located between the linescanner and the system connection box) are factory
preinstalled and supplied along with the system connection box.
For running the cables through the protective housing: open one grommet plate (on the bottom of the protective
housing) by loosening the three Allen-bolts. Use an appropriate grommet by considering the different cable outer
diameters:
Cable W1 (power supply): Ø 5 mm (0.2 in)
Cable W18 (Ethernet): Ø 6 mm (0.24 in)
Cable W3 (Alarm/Trigger): Ø 7 mm (0.28 in)
Feed the cable through the grommets so that grommet is approximately 400 mm (15.7 in) away from the
linescanner connectors (round plugs). Place the grommet plate over the grommets as shown in the figure below.
Be careful to have the cable identification plates pointed toward the system connection box (longer end of the
cables). Close unused holes with the blind grommets then close the grommet plate.
22

Figure 4-2: Protective Housing with Protective Channel

Linescanner
Protective
housing
Protective
channel
Window holder
2x M6 nuts
System Installation – with
Accessories, page 48.