Technical specifications
Article number
General information
Firmware version
Usable terminal block
Color code for module-specific color identifica‐
tion plate
Engineering with
Operating mode
Redundancy
Supply voltage
Rated value (DC)
permissible range, lower limit (DC)
permissible range, upper limit (DC)
Reverse polarity protection
Input current
Current consumption (rated value)
Current consumption, max.
Encoder supply
Output current
24 V encoder supply
Power
Power available from the backplane bus
Power loss
Power loss, typ.
Address area
Address space per module
32
FW update possible
SPPA-T3000 can be configured/integrated
from version
DI
Redundancy capability
up to 60 °C, max.
up to 70 °C, max.
24 V
Short-circuit protection
6DL1131-6BH00-0EH1
V1.0
Yes
TB type H1 and M1
CC01
V8.0
Yes
Yes; With TB type M1
24 V
19.2 V
28.8 V
Yes
60 mA; without sensor supply
120 mA; without sensor supply
2 A; 1 A when mounted vertically; see derating in‐
formation in Equipment Manual
1 A; See derating information in Equipment Manual
Yes
Yes; electronic (response threshold 0.7 A to 1.3 A;
for IO redundancy up to 2.6 A) Ensure sufficient
low-resistance cable routing to the sensor/actuator
in order to attain the response threshold. Depend‐
ing on the cable cross-section used, there may be
constraints regarding the usable length of cable
80 mW
3.6 W; Maximum value (taking the max. encoder
current and the max. operating voltage into ac‐
count)