Article number
Hardware configuration
Automatic encoding
Digital inputs
Digital inputs, parameterizable
Input characteristic curve in accordance with IEC
61131, type 1
Input characteristic curve in accordance with IEC
61131, type 2
Input characteristic curve in accordance with IEC
61131, type 3
Pulse extension
Time stamping
Time stamp (with precision of 1 ms)
Edge evaluation
Input voltage
Encoder
Connectable encoders
Interrupts/diagnostics/status information
Diagnoses
Diagnostics indication LED
Potential separation
Potential separation channels
DI 16x24VDC HA
Equipment Manual, 10/2020, A5E39265608-AD
Address space per module, max.
Mechanical coding element
Length
for signal "0"
for signal "1"
2-wire sensor
– permissible quiescent current (2-wire
sensor), max.
Diagnostic information readable
Monitoring the supply voltage
– parameterizable
Monitoring of encoder power supply
Short-circuit to M
MAINT LED
Monitoring of the supply voltage (PWR-LED)
Channel status display
for channel diagnostics
for module diagnostics
Technical specifications
6DL1131-6BH00-0EH1
24 byte; Without SOE: PII: 2 bytes, +2 bytes for QI
information, +1 byte of PROFINET status data; PIO:
1 byte of PROFINET status data; with SOE: PII: 2
bytes, +18 bytes for SOE (if 1 ms time stamp is
used), +2 bytes for QI information, +1 byte of PRO‐
FINET status data; PIO: 1 byte PROFINET status data
Yes
Yes
Yes
No
Yes
Yes
off, 50 ms, 100 ms, 200 ms, 500 ms, 1 s, 2 s
Yes; Resolution 10 ms
Yes; Resolution 1ms
Yes; rising edge, falling edge, edge change
-30 to +5 V
+11 to +30V
Yes
1.5 mA
Yes
Yes; Module-wise
Yes
Yes
Yes; Encoder supply to M, channel by channel
Yes; Yellow LED
Yes; green PWR LED
Yes; green LED
Yes; red LED
Yes; green/red LED