Parameters
6.1
Module/channel parameters
Definition
Module/channel parameters are specific parameters whose configuration can affect the entire
module or channels.
Description
The following module/channel parameters are available:
Table 6-1
Parameters and their defaults
Parameter
Diagnostics, Missing supply
voltage L+ (Page 20)
IO redundancy (Page 21)
Diagnostics, Short-circuit to
ground (Page 21)
Diagnostics, Wire break
(Page 21)
1
Wire-break check (Page 21)
Channel activated
(Page 22)
Input delay (Page 22)
2
DI 16x24VDC HA
Equipment Manual, 10/2020, A5E39265608-AD
Value range
•
Enabled
•
Disabled
•
None
•
2 modules
•
Enabled
•
Disabled
•
Enabled
•
Disabled
•
Enabled
•
Disabled
•
Enabled
•
Disabled
•
None
•
0.05 ms
•
0.1 ms
•
0.4 ms
•
0.8 ms
•
1.6 ms
•
3.2 ms
•
12.8 ms
•
20 ms
Default
Parameter re‐
assignment in
RUN
Enabled
Yes
None
No
Enabled
Yes
Enabled
Yes
Enabled
Yes
Enabled
Yes
3.2 ms
Yes
6
Efficiency range
Module
Module
Channel
Channel
Channel
Channel
Channel
19