Section 6 - Technical Data; Operational Limitations (English); Temperatures And Flows; Voltage Limitations - Johnson Controls YORK YCAL0041EC Installation Operation & Maintenance

Air-cooled liquid chillers hermetic scroll
Table of Contents

Advertisement

Technical Data
TABLE 2 – TEMPERATURES AND FLOWS
LEAVING WATER
TEMPERATURE (°F)
YCAL
MIN
0041
40
0045
40
0051
40
0055
40
0061
40
0065
40
0071
40

VOLTAGE LIMITATIONS

The following voltage limitations are absolute and opera-
tion beyond these limitations may cause serious damage
to the compressor.
TABLE 3 – VOLTAGE LIMITATIONS
UNIT POWER
200-3-60
230-3-60
380-3-60
460-3-60
575-3-60
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK Offi ce for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK Offi ce for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
4. For operation at temperatures below 25°F (-3.9°C), the optional Low Ambient Kit will need to be installed on the system.
5. For operation at temperatures above 115°F (46.1°C), the optional High Ambient Kit will need to be installed on the system.
44

SECTION 6 - TECHNICAL DATA

OPERATIONAL LIMITATIONS (ENGLISH)

ENGLISH
COOLER FLOW (GPM)
MAX
55
55
55
55
55
55
55
MIN.
MAX.
180
220
207
253
355
415
414
506
517
633
MIN
MAX
40
200
40
200
40
200
60
300
60
300
60
300
60
300
Excessive fl ow will cause damage to
the cooler. Do not exceed max. cooler
flow. Special care should be taken
when multiple chillers are fed by a
single pump.
FORM 150.66-NM1 (708)
AIR ON CONDENSER (°F)
MIN
MAX
0
125
0
125
0
125
0
125
0
125
0
125
0
125