Power Supply PS1000-A6-48.5

AC Input

5
AC Input
AC input
AC input range
Allowed voltage L or N to earth Max.
Input frequency
Turn-on voltage
Shut-down voltage
External input protection
Input current
1
Power factor
2
Crest factor
Start-up delay
Rise time
Turn-on overshoot
External input protection See recommendations in chapter 25.3.
1
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
2
The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Figure 5.1
Nom.
AC 100-240V
Min.
85-264Vac
Min.
264-300Vac
300Vac
Nom.
50–60Hz
Typ.
80Vac
Typ.
70Vac
Typ.
55Vac
See recommendations in chapter 25.3.
AC 100V
AC 120V
Typ.
2.82A
2.32A
Typ.
0.99
0.99
Typ.
1.5
Typ.
300ms
290ms
Typ.
63ms
63ms
Typ.
210ms
210ms
Max.
200mV
200mV
P
OUT
Input voltage range
Suitable for TN-, TT- and IT mains networks
Continuous operation
Below 90Vac, reduce output current according
to Figure 5.5.
For maximal 500ms
Continuous according to IEC 62477-1
±6%
Steady-state value, see Figure 5.1
Steady-state value, see Figure 5.1
Dynamic value for maximal 250ms
AC 230V
1.20A
At 48V, 5.4A, see Figure 5.3
0.98
At 48V, 5.4A, see Figure 5.4
1.5
1.65
At 48V, 5.4A
240ms
See Figure 5.2
63ms
At 48V, 5.4A const. current load,
0mF load capacitance,
see Figure 5.2
210ms
At 48V, 5.4A const. current load,
5mF load capacitance,
see Figure 5.2
200mV
See Figure 5.2
R ated
input range
max.
500ms
85V
264V
V
IN
300Vac
9