Power Supply PS1000-A6-48.5

Protection Features

19
Protection Features
Output protection
Output over-voltage protection
Degree of protection
Penetration protection
Over-temperature protection
Input transient protection
Internal input fuse
Electronically protected against overload, no-load and short-circuits.
In case of a protection event, audible noise may occur.
Typ. 58.5Vdc
Max. 60Vdc
IP 20
> 4mm
Yes
MOV
(Metal Oxide Varistor)
Included
In case of an internal power supply defect,
a redundant circuit limits the maximum output
voltage.
The output shuts down and automatically
attempts to restart.
EN/IEC 60529
E.g. screws, small parts
Output shut-down with automatic restart.
The temperature sensor is installed on critical
components inside the unit and turns the unit
off in safety critical situations (e.g. de-rating
requirements not observed, high ambient
temperature, ventilation obstructed or the
mounting orientation de-rating is not followed).
There is no correlation between the operating
temperature and turn-off temperature since this
is dependent on input voltage, load
and installation methods.
For protection values see chapter 17 (EMC).
Not user replaceable slow-blow high-braking
capacity fuse